| Time period (local standard time) | Occupancy (Monday to Friday) | Occupancy (Saturday and Sunday) | Artificial lighting (Monday to Friday) | Artificial lighting (Saturday and Sunday) | Air-conditioning (Monday to Friday) | Air-conditioning (Saturday and Sunday) |
|---|---|---|---|---|---|---|
| 12:00am to 1:00am | 0% | 0% | 5% | 5% | Off | Off |
| 1:00am to 2:00am | 0% | 0% | 5% | 5% | Off | Off |
| 2:00am to 3:00am | 0% | 0% | 5% | 5% | Off | Off |
| 3:00am to 4:00am | 0% | 0% | 5% | 5% | Off | Off |
| 4:00am to 5:00am | 0% | 0% | 5% | 5% | Off | Off |
| 5:00am to 6:00am | 0% | 0% | 5% | 5% | Off | Off |
| 6:00am to 7:00am | 0% | 0% | 5% | 5% | Off | Off |
| 7:00am to 8:00am | 0% | 0% | 5% | 5% | Off | On |
| 8:00am to 9:00am | 0% | 20% | 100% | 100% | Off | On |
| 9:00am to 10:00am | 0% | 70% | 10% | 10% | Off | On |
| 10:00am to 11:00am | 0% | 70% | 10% | 10% | Off | On |
| 11:00am to 12:00pm | 0% | 70% | 10% | 10% | On | On |
| 12:00pm to 1:00pm | 20% | 20% | 100% | 100% | On | On |
| 1:00pm to 2:00pm | 70% | 70% | 5% | 5% | On | On |
| 2:00pm to 3:00pm | 70% | 70% | 5% | 5% | On | On |
| 3:00pm to 4:00pm | 70% | 70% | 5% | 5% | On | On |
| 4:00pm to 5:00pm | 70% | 70% | 5% | 5% | On | On |
| 5:00pm to 6:00pm | 20% | 20% | 100% | 100% | On | On |
| 6:00pm to 7:00pm | 20% | 20% | 100% | 100% | On | On |
| 7:00pm to 8:00pm | 70% | 70% | 100% | 100% | On | On |
| 8:00pm to 9:00pm | 70% | 70% | 5% | 5% | On | On |
| 9:00pm to 10:00pm | 70% | 70% | 5% | 5% | On | On |
| 10:00pm to 11:00pm | 70% | 70% | 5% | 5% | On | On |
| 11:00pm to 12:00am | 10% | 10% | 100% | 100% | On | On |
Table Notes
The occupancy profile is expressed as a percentage of the maximum number of people that can be accommodated in the building.
The artificial lighting profile is expressed as a percentage of the maximum illumination power density permitted under Part J7.
The air-conditioning profile is expressed as the plant status.
Table for S35C2 Modelling profiles
Same wording in NCC 2022 Volume One. See NCC 2022 Volume One Table S35C2h.