Table · NCC 2025 Volume One

Table S35C2j Occupancy and operation profiles of a Class 9b school

Specification 35 Modelling profiles for J1V3

Open Table S35C2j on NCC Online ↗
Time period (local standard time)Occupancy (Monday to Friday)Artificial lighting (Monday to Friday)Appliances and equipment (Monday to Friday)Air-conditioning (Monday to Friday)
12:00am to 1:00am0%0%5%Off
1:00am to 2:00am0%0%5%Off
2:00am to 3:00am0%0%5%Off
3:00am to 4:00am0%0%5%Off
4:00am to 5:00am0%0%5%Off
5:00am to 6:00am0%0%5%Off
6:00am to 7:00am0%0%5%Off
7:00am to 8:00am5%20%30%On
8:00am to 9:00am75%85%85%On
9:00am to 10:00am90%95%95%On
10:00am to 11:00am90%95%95%On
11:00am to 12:00pm90%95%95%On
12:00pm to 1:00pm50%60%70%On
1:00pm to 2:00pm50%60%70%On
2:00pm to 3:00pm90%95%95%On
3:00pm to 4:00pm70%90%80%On
4:00pm to 5:00pm50%70%60%On
5:00pm to 6:00pm20%20%20%Off
6:00pm to 7:00pm20%20%20%Off
7:00pm to 8:00pm20%20%20%Off
8:00pm to 9:00pm10%5%10%Off
9:00pm to 10:00pm5%0%5%Off
10:00pm to 11:00pm5%0%5%Off
11:00pm to 12:00am5%0%5%Off

Table Notes

The occupancy profile is expressed as a percentage of the maximum number of people that can be accommodated in the building.

The artificial lighting profile is expressed as a percentage of the maximum illumination power density permitted under Part J7.

The appliances and equipment profile is expressed as a percentage of the maximum internal heat gain in S35C2l.

The air-conditioning profile is expressed as the plant status.

Saturday and Sunday profiles are 5% continuous artificial lighting and 5% continuous appliances and equipment, where there is no occupancy and the air-conditioning is “off”.

Table for S35C2 Modelling profiles

Changed since NCC 2022. See NCC 2022 Volume One Table S35C2j, or show what changed.

Time period (local standard time) | Occupancy (Monday to Friday) … Air-conditioning (Monday to Friday) 12:00am to 1:00am | 0% | 5% 0% | 5% | Off 1:00am to 2:00am | 0% | 5% 0% | 5% | Off 2:00am to 3:00am | 0% | 5% 0% | 5% | Off 3:00am to 4:00am | 0% | 5% 0% | 5% | Off 4:00am to 5:00am | 0% | 5% 0% | 5% | Off 5:00am to 6:00am | 0% | 5% 0% | 5% | Off 6:00am to 7:00am | 0% | 5% 0% | 5% | Off 7:00am to 8:00am | 5% | 30% 20% | 30% | On 8:00am to 9:00am | 75% | … | 95% | On 12:00pm to 1:00pm | 50% | 80% 60% | 70% | On 1:00pm to 2:00pm | 50% | 80% 60% | 70% | On 2:00pm to 3:00pm | 90% | … | 20% | Off 8:00pm to 9:00pm | 10% | 10% 5% | 10% | Off 9:00pm to 10:00pm | 5% | 5% 0% | 5% | Off 10:00pm to 11:00pm | 5% | 5% 0% | 5% | Off 11:00pm to 12:00am | 5% | 5% 0% | 5% | Off Table Notes The occupancy profile is … where there is no occupancy and the air-conditioning is “off”.

Removed words are struck through; added words are highlighted. Comparison of the text only.

Defined terms used