Table · NCC 2025 Volume One

Table S35C2m Heated water supply consumption rates

Specification 35 Modelling profiles for J1V3

Open Table S35C2m on NCC Online ↗
ApplicationDaily consumption rate at 60°C
Residential part of a hotel or motel100 L/sole-occupancy unit
Dormitory, boarding house, guest house, hostel, lodging house and backpackers accommodation50 L/person
Office, laboratory, shop and assembly building4 L/person
Dining room, restaurant and cafe9 L/meal
Health-care building, ward area70 L/patient
School7 L/person
Other applications4 L/person

Residential part of a school, accommodation for the aged, children or people with a disability and a detention centre or a health-care building which accommodates members of staff

Class 9c building

Table for S35C2 Modelling profiles

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One Table S35C2m.

Defined terms used