Tasmania variation · NCC 2025 Volume One

TAS F4D14 Installation of closet fixtures

TAS Part F4 Sanitary and other facilities

Open on NCC Online ↗

Insert TAS clause F4D14 in clause F4D14 as follows:

(1) If a sufficient sewerage system is not available, an authorised alternative means of disposal of sewage may be installed.

(2) If sanitary facilities are not water-flushed, the following provisions apply:

A pit latrine, an incinerating toilet, a chemical toilet, a removable pan or a non-flushing urinal must not be within 2 m of a building containing habitable rooms.

The floor on which a removable pan is placed must be impervious.

A room containing a composting toilet must be separated from habitable rooms by way of a permanently ventilated air lock (which may be a circulation space).

The minimum ventilation required under (c) shall be the greater of—

8000 mm2; or

1/500th of the floor area of the circulation space.

Access for maintenance or removal of waste from a composting toilet must be by way of an access door which opens directly to the outside of the building.

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One TAS F4D14.