Tasmania variation · NCC 2025 Volume One

TAS G5P1 Bushfire resistance

TAS Part G5 Construction in bushfire prone areas · varies G5P1 Bushfire resistance

Open on NCC Online ↗

Delete clause G5P1 and insert TAS G5P1 as follows:

A building that is constructed in a designated bushfire prone area must be designed and constructed to—

reduce the risk of ignition from a design bushfire with an annual exceedance probability not more than 1:100 years, or 1:200 years for a Class 9 building; and

take account of the assessed duration and intensity of the fire actions of the design bushfire; and

be designed to prevent internal ignition of the building and its contents; and

maintain the structural integrity of the building for the duration of the design bushfire.

Applications

G5P1 applies in a designated bushfire prone area to—

a Class 2 or 3 building; and

a Class 9a health-care building; and

a Class 9b—

early childhood centre; and

primary or secondary school; and

a Class 9c residential care building; and

a Class 10a building or deck immediately adjacent or connected to a building of a type listed in (a) to (d).

Notes

For additional requirements relating to bushfire prone areas, refer to the Director’s Determinations on Bushfire Hazard Areas – current versions available at www.cbos.tas.gov.au

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One TAS G5P1.

The national clause

Other states and territories