TAS I11D3 Cupola charging platform
TAS Part I11 Foundries
Delete clause I11D3 and insert TAS I11D3 as follows:
(1) The floors of cupola charging platforms must be—
of heavy timber or non-slip steel plate; and
securely fixed in position; and
level.
(2) All parts of the cupola charging platform must be covered by a roof not less than 3 m above the platform.
(3) A cupola charging platform must have—
a wall, not less than 1 m high, measured from the floor of the platform, constructed to surround the platform; and
the side between the top of the wall and the roof suitably waterproofed an ventilated.
(4) A properly constructed access stair or ramp must be provide to give access to every cupola charging platform and must comply with AS 1657.
Changed since NCC 2022. See NCC 2022 Volume One TAS I11D3, or show what changed.