Tasmania variation · NCC 2025 Volume One
TAS I12D5 Required exits
TAS Part I12 Premises for manufacture or processing of glass reinforced plastics
Delete clause I12D5 and insert TAS I12D5 as follows:
(1) Each fire-separated section of a building which is a work place must have at least two exits for escape purposes and the number and location of exits must be such that any point on the floor is not further than 20 m from one of the exits.
(2) Only exits with vertically hinged swinging doors may be considered as exits for the purposes of this clause.
Changed since NCC 2022. See NCC 2022 Volume One TAS I12D5, or show what changed.
Delete clause I12D5 and insert TAS I12D5 as follows: (1) Each fire-separated section of a building which is a … be considered as exits for the purposes of this clause.
Removed words are struck through; added words are highlighted. Comparison of the text only.