13.2.2 Building fabric thermal insulation
Part 13.2 Building fabric · NCC 2019: 3.12.1.1
(1) Where required, insulation must comply with AS/NZS 4859.1 and be installed so that it—
abuts or overlaps adjoining insulation other than at supporting members such as columns, studs, noggings, joists, furring channels and the like where the insulation must butt against the member; and
forms a continuous barrier with ceilings, walls, bulkheads, floors or the like that inherently contribute to the thermal barrier; and
does not affect the safe or effective operation of a domestic service or fitting.
(2) Where required, reflective insulation must be installed with—
the necessary airspace, to achieve the required R-Value between a reflective side of the reflective insulation and a building lining or cladding; and
the reflective insulation closely fitted against any penetration, door or window opening; and
the reflective insulation adequately supported by framing members; and
each adjoining sheet of roll membrane being—
overlapped greater than or equal to 150 mm; or
taped together.
(3) Where required, bulk insulation must be installed so that—
it maintains its position and thickness, other than where it crosses roof battens, water pipes, electrical cabling or the like; and
in a ceiling, where there is no bulk insulation or reflective insulation in the external wall beneath, it overlaps the external wall by greater than or equal to 50 mm.