ABCB Housing Provisions 2022
Part 13.2 Building fabric
64 clauses · Open on NCC Online ↗
- 13.2.1 Application of Part 13.2 NSW NTThe provisions of 13.2.2 to 13.2.6 apply to— a Class 1 building; and a Class 10a building with a conditioned space. (2) The provisions of 13.2.7…
- 13.2.2 Building fabric thermal insulation NTWhere required, insulation must comply with AS/NZS 4859.1 and be installed so that it— abuts or overlaps adjoining insulation other than at…
- Table 13.2.3a Pitched roof with horizontal ceiling – minimum R-Value for ceiling insulation: climate zone 1 – single storey dwellingRoof ventilation | Reflective insulation under-roof | Under-roof insulation R-Value | SA ≤ 0.23 | 0.23 < SA ≤ 0.32 | 0.32 < SA ≤ 0.42 | 0.42 < SA ≤…
- Table 13.2.3b Pitched roof with horizontal ceiling – minimum R-Value for ceiling insulation: climate zone 1 – two (or more) storey dwellingRoof ventilation | Reflective insulation under-roof | Under-roof insulation R-Value | SA≤ 0.23 | 0.23< SA≤0.32 | 0.32< SA≤0.42 | 0.42< SA≤0.53 |…
- Table 13.2.3c Pitched roof with horizontal ceiling – minimum R-Value for ceiling insulation: climate zone 2Roof ventilation | Reflective insulation under-roof | Under-roof insulation R-Value | SA ≤ 0.23 | 0.23 < SA ≤ 0.32 | 0.32 < SA ≤ 0.42 | 0.42 < SA ≤…
- Table 13.2.3d Pitched roof with horizontal ceiling – minimum R-Value for ceiling insulation: climate zone 3Roof ventilation | Reflective insulation under-roof | Under-roof insulation R-Value | SA ≤ 0.23 | 0.23 < SA ≤ 0.32 | 0.32 < SA ≤ 0.42 | 0.42 < SA ≤…
- Table 13.2.3e Pitched roof with horizontal ceiling – minimum R-Value for ceiling insulation: climate zone 4Roof ventilation | Reflective insulation under-roof | Under-roof insulation R-Value | SA ≤ 0.23 | 0.23 < SA ≤ 0.64 Vented | Yes | < 0.5 | 3.0 | 3.5…
- Table 13.2.3f Pitched roof with horizontal ceiling – minimum R-Value for ceiling insulation: climate zone 5Roof ventilation | Reflective insulation under-roof | Under-roof insulation R-Value | SA ≤ 0.42 | 0.42 < SA ≤ 0.64 Vented | Yes | < 0.5 | 3.0 | 2.5…
- Table 13.2.3g Pitched roof with horizontal ceiling – minimum R-Value for ceiling insulation: climate zone 6Roof ventilation | Reflective insulation under-roof | Under-roof insulation R-Value | 0.23 ≤ SA ≤ 0.64 | 0.64 < SA ≤ 0.96 Vented | Yes | < 1.0 | 4.0…
- Table 13.2.3h Pitched roof with horizontal ceiling – minimum R-Value for ceiling insulation: climate zone 7Roof ventilation | Reflective insulation under-roof | Under-roof insulation R-Value | SA ≤ 0.23 | 0.23 < SA ≤ 0.32 | 0.32 < SA ≤ 0.42 | 0.42 < SA ≤…
- Table 13.2.3i Pitched roof with horizontal ceiling – minimum R-Value for ceiling insulation: climate zone 8Roof ventilation | Reflective insulation under-roof | Under-roof insulation R-Value | SA ≤ 0.23 | 0.23 < SA ≤ 0.32 | 0.32 < SA ≤ 0.42 | 0.42 < SA ≤…
- Table 13.2.3j Flat, skillion or cathedral roof – minimum R-Value for ceiling insulation: climate zone 1 – single storey dwellingReflective insulation under-roof | SA ≤ 0.23 | 0.23 < SA ≤ 0.32 | 0.32 < SA ≤ 0.42 | 0.42 < SA ≤ 0.53 | 0.53 < SA ≤ 0.64 Yes | 1.0 | 2.0 | 2.0 | 4.0…
- Table 13.2.3k Flat, skillion or cathedral roof – minimum R-Value for ceiling insulation: climate zone 1 – two (or more) storey dwellingReflective insulation under-roof | SA ≤ 0.23 | 0.23 < SA ≤ 0.32 | 0.32 < SA ≤ 0.42 | 0.42 < SA ≤ 0.53 | 0.53 < SA ≤ 0.64 Yes | 1.5 | 1.5 | 2.0 | 3.0…
- Table 13.2.3l Flat, skillion or cathedral roof – minimum R-Value for ceiling insulation: climate zone 2Reflective insulation under-roof | SA ≤ 0.23 | 0.23 < SA ≤ 0.32 | 0.32 < SA ≤ 0.42 | 0.42 < SA ≤ 0.53 | 0.53 < SA ≤ 0.64 Yes | 2.5 | 2.5 | 2.5 | 2.5…
- Table 13.2.3m Flat, skillion or cathedral roof – minimum R-Value for ceiling insulation: climate zone 3Reflective insulation under-roof | SA ≤ 0.23 | 0.23 < SA ≤ 0.32 | 0.32 < SA ≤ 0.42 | 0.42 < SA ≤ 0.53 | 0.53 < SA ≤ 0.64 Yes | 2.0 | 2.0 | 2.5 | 2.5…
- Table 13.2.3n Flat, skillion or cathedral roof – minimum R-Value for ceiling insulation: climate zone 4Reflective insulation under-roof | SA ≤ 0.64 Yes | 3.0 No | 3.5 Table Notes SA = solar absorptance. The R-Value can be achieved by installing…
- Table 13.2.3o Flat, skillion or cathedral roof – minimum R-Value for ceiling insulation: climate zone 5Reflective insulation under-roof | SA ≤ 0.64 Yes | 2.5 No | 3.0 Table Notes SA = solar absorptance. The R-Value can be achieved by installing…
- Table 13.2.3p Flat, skillion or cathedral roof – minimum R-Value for ceiling insulation: climate zone 6Reflective insulation under-roof | 0.23 ≤ SA < 0.64 | SA = 0.64 | 0.64 < SA ≤ 0.96 Yes | 4.0 | 3.5 | 4.0 No | 4.0 | 4.0 | 4.0 Table Notes SA = solar…
- Table 13.2.3q Flat, skillion or cathedral roof – minimum R-Value for ceiling insulation: climate zone 7Reflective insulation under-roof | SA ≤ 0.23 | 0.23 < SA ≤ 0.32 | 0.32 < SA ≤ 0.42 | 0.42 < SA ≤ 0.53 | 0.53 < SA ≤ 0.64 | 0.64 < SA ≤ 0.73 | 0.73 <…
- Table 13.2.3r Flat, skillion or cathedral roof – minimum R-Value for ceiling insulation: climate zone 8Reflective insulation under-roof | SA ≤ 0.23 | 0.23 < SA ≤ 0.32 | 0.32 < SA ≤ 0.42 | 0.42 < SA ≤ 0.53 | 0.53 < SA ≤ 0.64 | 0.64 < SA ≤ 0.73 | 0.73 <…
- Table 13.2.3s Metal-framed pitched roof with horizontal ceiling – minimum Total R-Value of ceiling to account for thermal bridgingMinimum ceiling insulation R-Value from Tables 13.2.3a to 13.2.3i as applicable | Minimum ceiling Total R-Value 1.5 | 1.38 2.0 | 1.74 2.5 | 2.09 3.0…
- Table 13.2.3t Metal-framed flat, skillion or cathedral roof – minimum Total R-Value to account for thermal bridgingMinimum ceiling insulation R-Value from Tables 13.2.3j to 13.2.3r | Minimum Total R-Value to account for thermal bridging – heat flow down | Minimum…
- Table 13.2.3u Metal-framed flat, skillion or cathedral roof – thermal bridging mitigationMinimum ceiling insulation R-Value from Tables 13.2.3j to 13.2.3r | Option 1 – increase insulation between roof frame members to specified minimum…
- Table 13.2.3v Direction of heat flowClimate zone | Direction of heat flow 1 | Down 2 (altitude less than 300 m) | Down 2 (altitude 300 m or more) | Down and up 3 | Down and up 4 | Up 5…
- Table 13.2.3w Adjusted minimum R-Value of ceiling insulation required to compensate for loss of ceiling insulation areaPercentage of ceiling area uninsulated | Minimum R-Value of ceiling insulation required to satisfy 13.2.3(1) and (3) 1.0 | 1.5 | 2.0 | 2.5 | 3.0 |…
- Table 13.2.3x Total R-Value for roofs constructed with insulated sandwich panelsClimate zone | SA ≤ 0.23 | 0.23 < SA ≤ 0.32 | 0.32 < SA ≤ 0.42 | 0.42 < SA ≤ 0.53 | 0.53 < SA ≤ 0.64 | 0.64 < SA ≤ 0.73 | 0.73 < SA ≤ 0.85 | 0.85 <…
- 13.2.3 Roofs and ceilings NSW NTRoof and ceiling insulation must achieve the minimum R-Value— in climate zone 1, in accordance with Tables 13.2.3a, 13.2.3b, 13.2.3j and 13.2.3k as…
- Table 13.2.4 Roof lights – Total System SHGCRoof light shaft index Note 1 | Total area of roof lights up to 3.5% of the floor area of the room or space | Total area of roof lights more than…
- 13.2.4 Roof lights NSW NTRoof lights (including any associated shaft and diffuser) serving a habitable room or an interconnecting space such as a corridor, hallway, stairway…
- Table 13.2.5a Concrete block walls – minimum insulation R-Value: climate zone 1SA | Overhang (mm) | Wall height (m) ≤ 2.4 | > 2.4 to ≤ 2.7 | > 2.7 to ≤ 3.0 | > 3.0 to ≤ 3.6 ≤ 0.3 | 0 | X | X | X | X > 0 to ≤ 300 | Reflective |…
- Table 13.2.5b Lightweight walls – minimum insulation R-Value: climate zone 1SA | Overhang (mm) | Wall height (m) ≤ 2.4 | > 2.4 to ≤ 2.7 | > 2.7 to ≤ 3.0 | > 3.0 to ≤ 3.6 ≤ 0.3 | 0 | X | X | X | X > 0 to ≤ 300 | 2.5 | X | X |…
- Table 13.2.5c Masonry veneer wall – minimum insulation R-Value: climate zone 2SA | Overhang (mm) | Wall height (m) ≤ 2.4 | > 2.4 to ≤ 2.7 | > 2.7 to ≤ 3.0 | > 3.0 to ≤ 3.6 ≤ 0.35 | 0 | X | X | X | X > 0 to ≤ 300 | 2.0 | X | X…
- Table 13.2.5d Masonry cavity wall – minimum insulation R-Value: climate zone 2SA | Overhang (mm) | Wall height (m) ≤ 2.4 | > 2.4 to ≤ 2.7 | > 2.7 to ≤ 3.0 | > 3.0 to ≤ 3.6 ≤ 0.35 | 0 | 0.25 | 0.25 | 0.25 | 0.51 > 0 to ≤ 300 |…
- Table 13.2.5e Concrete block wall – minimum insulation R-Value: climate zone 3SA | R-Value ≤ 0.7 | 1.5 Table Notes SA = solar absorptance. R-Values listed are for the labelled, declared R-Value of insulation.
- Table 13.2.5f Lightweight wall – minimum insulation R-Value: climate zone 3SA | Overhang (mm) | Wall height (m) ≤ 2.4 | > 2.4 to ≤ 2.7 | > 2.7 to ≤ 3.0 | > 3.0 to ≤ 3.6 ≤ 0.3 | 0 | X | X | X | X > 0 to ≤ 300 | 2.5 | X | X |…
- Table 13.2.5g Masonry veneer wall – minimum insulation R-Value: climate zone 4SA | Overhang (mm) | Wall height (m) ≤ 2.4 | > 2.4 to ≤ 2.7 | > 2.7 to ≤ 3.0 | > 3.0 to ≤ 3.6 ≤ 0.35 | 0 | 2.0 | 2.5 | 2.5 | X > 0 to ≤ 300 | 2.0 |…
- Table 13.2.5h Masonry cavity wall – minimum insulation R-Value: climate zone 4SA | Overhang (mm) | Wall height (m) ≤ 2.4 | > 2.4 to ≤ 2.7 | > 2.7 to ≤ 3.0 | > 3.0 to ≤ 3.6 ≤ 0.35 | 0 | 0.25 | 0.25 | 0.51 | 0.75 > 0 to ≤ 300 |…
- Table 13.2.5i Masonry veneer wall – minimum insulation R-Value: climate zone 5SA | Overhang (mm) | Wall height (m) ≤ 2.4 | > 2.4 to ≤ 2.7 | 2.7 to ≤ 3.0 | > 3.0 to ≤ 3.6 ≤ 0.35 | 0 | 1.5 | 2.0 | 2.0 | 2.5 > 0 to ≤ 300 | 1.5 |…
- Table 13.2.5j Masonry cavity wall – minimum insulation R-Value: climate zone 5SA | Overhang (mm) | Wall height (m) ≤ 2.4 | > 2.4 to ≤ 2.7 | > 2.7 to ≤ 3.0 | > 3.0 to ≤ 3.6 ≤ 0.35 | 0 | 0.0 | 0.0 | 0.25 | 0.25 > 0 to ≤ 300 |…
- Table 13.2.5k Masonry veneer wall – minimum insulation R-Value: climate zone 6SA | Overhang (mm) | Wall height (m) ≤ 2.4 | > 2.4 to ≤ 2.7 | > 2.7 to ≤ 3.0 | > 3.0 to ≤ 3.6 ≤ 0.35 | 0 | 2.0 | 2.4 | X | X > 0 to ≤ 300 | 2.4 |…
- Table 13.2.5l Masonry cavity wall – minimum insulation R-Value: climate zone 6SA | Overhang (mm) | Wall height (m) ≤ 2.4 | > 2.4 to ≤ 2.7 | > 2.7 to ≤ 3.0 | > 3.0 to ≤ 3.6 ≤ 0.35 | 0 | 0.51 | 0.62 | 1.08 | 1.44 > 0 to ≤ 300 |…
- Table 13.2.5m Masonry veneer wall – minimum insulation R-Value: climate zone 7SA | Overhang (mm) | Wall height (m) ≤ 2.4 | > 2.4 to ≤ 2.7 | > 2.7 to ≤ 3.0 | > 3.0 to ≤ 3.6 ≤ 0.35 | 0 | 1.5 | 1.5 | 1.5 | 2.4 > 0 to ≤ 300 | 2.0…
- Table 13.2.5n Masonry cavity wall – minimum insulation R-Value: climate zone 7SA | Overhang (mm) | Wall height (m) ≤ 2.4 | > 2.4 to ≤ 2.7 | > 2.7 to ≤ 3.0 | > 3.0 to ≤ 3.6 ≤ 0.35 | 0 | 1.08 | 1.44 | X | X > 0.35 to ≤ 0.5 | 0 |…
- Table 13.2.5o Lightweight wall – minimum insulation R-Value: climate zone 8SA | Overhang (mm) | Wall height (m) ≤ 2.4 | > 2.4 to ≤ 2.7 | > 2.7 to ≤ 3.0 | > 3.0 to ≤ 3.6 ≤ 0.35 | 0 | 1.5 | 2.0 | 2.0 | X > 0 to ≤ 300 | 2.0 |…
- Table 13.2.5p Concrete block walls with internal lining fixed to a metal frame: minimum Total R-Value to account for thermal bridgingWall insulation R-Value from Tables 13.2.5a and 13.2.5e | Minimum Total R-Value to account for thermal bridging 0.5 | 0.94 1.0 | 1.15 1.5 | 1.66 2.0…
- Table 13.2.5q Lightweight metal-framed walls: minimum Total R-Value to account for thermal bridgingWall insulation R-Value required in accordance with 13.2.5(2) | Minimum Total R-Value to account for thermal bridging 1.0 | 1.32 1.5 | 1.64 2.0 |…
- Table 13.2.5r Masonry veneer metal-framed walls: minimum Total R-Value to account for thermal bridgingWall insulation from Tables 13.2.5c, 13.2.5g, 13.2.5i, 13.2.5k and 13.2.5m | Minimum Total R-Value to account for thermal bridging 1.5 | 1.79 2.0 |…
- Table 13.2.5s Concrete block walls with internal lining fixed to a metal frame – thermal bridging mitigationWall insulation R-Values from Tables 13.2.5a to 13.2.5e | Option 1 – increase insulation between wall framing to specified minimum R-Value | Option…
- Table 13.2.5t Lightweight metal-framed walls – thermal bridging mitigationWall insulation R-Value from Tables 13.2.5a to 13.2.5o | Thermal bridging mitigation 0 or reflective | Not required >0 to ≤1.5 | Either install…
- Table 13.2.5u Masonry veneer metal-framed walls – thermal bridging mitigationWall insulation R-Value from Tables 13.2.5c, 13.2.5g, 13.2.5i, 13.2.5k and 13.2.5m | Thermal bridging mitigation options > 0 | Either install…
- 13.2.5 External walls NSW NTExcept for the external wall of a sub-floor space below a suspended floor and lightweight wall construction, wall insulation must have a minimum…
- Table 13.2.6a Minimum R-Value of floor insulation where the floor is over an unenclosed spaceClimate zone | R-Value 1 | 2.0 2 | 2.0 3 | 1.5 4 | X 5 | X 6 | 4.0, or 3.5 if used in conjunction with a reflective airspace 7 8 Table Notes…
- Table 13.2.6b Minimum R-Value of subfloor wall insulation where the floor is over an enclosed subfloor space: climate zone 2Subfloor wall height (mm) | Minimum subfloor wall insulation R-Value ≤600 | 0.5 >600 to ≤900 | 1.0 >900 to ≤1200 | 1.5 >1200 to ≤1500 | 1.5 >1500 to…
- Table 13.2.6c Minimum R-Value of subfloor wall insulation where the floor is over an enclosed subfloor space: climate zone 3Subfloor wall height (mm) | Minimum subfloor wall insulation R-Value ≤600 | 0.5 >600 to ≤900 | 0.5 >900 to ≤1200 | 0.5 >1200 to ≤1500 | 0.5 >1500 to…
- Table 13.2.6d Minimum R-Value of floor and subfloor wall insulation where the floor is over an enclosed subfloor space: climate zone 4Subfloor wall height (mm) | Reflective insulation facing down over the subfloor space | Minimum subfloor wall insulation R-Value | Minimum suspended…
- Table 13.2.6e Minimum R-Value of floor and subfloor wall insulation where the floor is over an enclosed subfloor area: climate zone 5Subfloor wall height (mm) | Reflective insulation facing down over the subfloor surface | Minimum subfloor wall insulation R-Value | Minimum…
- Table 13.2.6f Minimum R-Value of floor and subfloor wall insulation where the floor is over an enclosed subfloor space: climate zone 6Subfloor wall height (mm) | Reflective insulation facing down over the subfloor area | Minimum subfloor wall insulation R-Value | Minimum suspended…
- Table 13.2.6g Minimum R-Value of floor and subfloor insulation where the floor is over an enclosed subfloor space: climate zone 7Subfloor wall height (mm) | Reflective insulation facing down over the subfloor space | Minimum subfloor wall insulation R-Value | Minimum suspended…
- Table 13.2.6h Minimum R-Value of floor and subfloor wall insulation where the floor is over an enclosed subfloor space: climate zone 8Subfloor wall height (mm) | Reflective insulation facing down over the subfloor space | Minimum subfloor wall insulation R-Value | Minimum suspended…
- Table 13.2.6i Metal-framed suspended floor — minimum Total R-Value for floor to account for thermal bridgingFloor insulation from Tables 13.2.6a and 13.2.6d to 13.2.6h as applicable | Floor covering | Minimum Total R-Value of floor 0.0 | Carpet | 0.36 0.0…
- Table 13.2.6j Metal-framed suspended floor — thermal bridging mitigationFloor insulation from Tables 13.2.6a and 13.2.6d to 13.2.6h as applicable | Option 1 – increase insulation between floor framing to specified…
- Table 13.2.6k Floor — direction of heat flowClimate zone | Direction of heat flow 1 | Up 2 | Up 3 | Up 4 | Down 5 | Down 6 | Down 7 | Down 8 | Down
- 13.2.6 Floors and subfloor walls NSW NTFloor insulation, where the floor is over an unenclosed space, must achieve the minimum R-Value in accordance with Table 13.2.6a. (2) Floor and…
- 13.2.7 Attached Class 10a buildings NSWA Class 10a building attached to a Class 1 building must— have an external fabric that achieves the required level of thermal performance for a…