Table · ABCB Housing Provisions 2022

Table 13.2.3a Pitched roof with horizontal ceiling – minimum R-Value for ceiling insulation: climate zone 1 – single storey dwelling

Part 13.2 Building fabric

Open Table 13.2.3a on NCC Online ↗
Roof ventilationReflective insulation under-roofUnder-roof insulation R-ValueSA ≤ 0.230.23 < SA ≤ 0.320.32 < SA ≤ 0.420.42 < SA ≤ 0.530.53 < SA ≤0 .64
VentedYes< 1.01.52.02.53.03.5
≥ 1.0 to < 1.51.51.52.02.53.0
≥ 1.51.52.02.02.02.0
No< 1.02.54.5XXX
≥ 1.0 to < 1.52.03.04.05.0X
≥ 1.52.02.53.04.05.0
StandardYes< 1.01.52.02.54.0X
≥ 1.0 to < 1.51.51.52.03.04.0
≥ 1.51.51.52.02.53.0
No< 1.03.5XXXX
≥ 1.0 to < 1.52.03.55.5XX
≥ 1.52.02.03.54.06.0

Table Notes

SA = solar absorptance.

A roof is considered ‘vented’ if it—

has one wind-driven roof ventilator per 50 m2 of ceiling area, with gable, eave or ridge vents; or

has one powered roof ventilator per 200 m2 of ceiling area, with gable, eave or ridge vents; or

is a tiled roof without sarking-type material at roof level.

If a roof is not ‘vented’, it is a ‘standard’ roof.

The R-Value of reflective insulation is not to be included in the R-Value of any under-roof or ceiling insulation.

R-Values listed are for the labelled, declared R-Value of insulation.

X = not permitted.

Table for 13.2.3 Roofs and ceilings

Same wording in ABCB Housing Provisions 2025. See ABCB Housing Provisions 2025 Table 13.2.3a.