Housing Provisions clause · ABCB Housing Provisions 2022

6.3.3 Bearers

Part 6.3 Structural steel members

Open 6.3.3 on NCC Online ↗

Structural steel bearers must comply with the following:

Effective bearer spacing must be determined in accordance with—

for single span joists — Table H1D6a and Figure H1D6d; and

for continuous span joists — Table H1D6b and Figure H1D6e.

Maximum acceptable bearer spans must be determined in accordance with—

for single spans — Tables 6.3.3a and 6.3.3c; and

for continuous spans — Tables 6.3.3b and 6.3.3d.

All loads along the bearer must be evenly distributed.

The difference in distance between supports for continuous span bearers must not be more than 10% of the span.

Fixing of joists and columns to structural steel bearers must comply with 6.3.7.

Bearers must be supported by structural steel columns that comply with 6.3.6 and are fixed in accordance with 6.3.7.

Table 6.3.3a Maximum bearer span (m) — single span — bearer supporting timber floor and 3 m high non-loadbearing internal wall

Steel section

Effective load width (m)

1.8

2.4

3.0

3.6

4.2

125 TFB

4.2

4.0

3.9

3.8

3.6

180 UB 16.1

5.6

5.4

5.3

5.1

4.7

200 UB 18.2

6.4

6.2

6.0

5.8

5.4

250 UB 25.7

8.3

8.0

7.8

7.6

7.1

250 x 150 x 9 RHS

9.3

9.0

8.8

8.6

8.4

250 x 150 x 5 RHS

8.0

7.8

7.6

7.1

6.6

310 UB 32.0

10.0

9.7

9.4

9.2

8.6

125 x 75 x 2 RHS

2.9

2.6

2.3

2.2

2.0

125 x 75 x 3 RHS

3.5

3.3

3.2

2.9

2.7

150 x 50 x 2 RHS

3.3

2.9

2.6

2.4

2.3

150 x 50 x 3 RHS

3.7

3.6

3.4

3.1

2.9

100 TFB

2.9

2,8

2.7

2.5

2.4

150 PFC

5.2

5.0

4.9

4.7

4.6

180 PFC

6.1

5.9

5.8

5.6

5.4

200 PFC

6.8

6.6

6.4

6.2

5.9

250 PFC

8.9

8.6

8.4

8.2

8.0

300 PFC

10.4

10.1

9.8

9.5

9.3

Table Notes

Load accounted for includes 0.53 kPa permanent floor, 0.92 kN/m permanent wall, permanent member self-weight, 1.5 kPa or 1.1 kN imposed.

Load combinations included are 1.35G and 1.25G+1.5Q for ULS and G + 0.7Q for SLS with a maximum deflection of span/300.

Bearers are assumed to have intermediate lateral restraints at joist locations and are considered fully laterally restrained.

Table 6.3.3b Maximum bearer span (m) — continuous span — bearer supporting timber floor and 3 m high non-loadbearing internal wall

Steel section

Effective load width (m)

1.8

2.4

3.0

3.6

4.2

125 TFB

5.2

4.6

4.2

3.9

3.6

180 UB 16.1

6.8

6.0

5.5

5.1

4.7

200 UB 18.2

7.7

6.9

6.2

5.8

5.4

250 UB 25.7

10.2

9.1

8.3

7.6

7.1

250 x 150 x 9 RHS

12.4

11.5

10.5

9.8

9.1

250 x 150 x 5 RHS

9.5

8.4

7.7

7.1

6.6

310 UB 32.0

12.3

11.0

10.0

9.2

8.6

125 x 75 x 2 RHS

2.9

2.6

2.3

2.2

2.0

125 x 75 x 3 RHS

4.0

3.5

3.2

2.9

2.7

150 x 50 x 2 RHS

3.3

2.9

2.6

2.4

2.3

150 x 50 x 3 RHS

4.2

3.7

3.4

3.1

2.9

100 TFB

3.4

3.0

2.7

2.5

2.4

150 PFC

6.5

5.8

5.3

4.9

4.6

180 PFC

7.8

6.9

6.3

5.8

5.4

200 PFC

8.5

7.6

6.9

6.4

5.9

250 PFC

11.6

10.4

9.5

8.7

8.2

300 PFC

13.4

12.0

10.9

10.1

9.4

Table Notes

Load accounted for includes 0.53 kPa permanent floor, 0.92 kN/m permanent wall, permanent member self-weight, 1.5 kPa or 1.1 kN imposed.

Load combinations included are 1.35G and 1.25G+1.5Q for ULS and G + 0.7Q for SLS with a maximum deflection of span/300.

Bearers are assumed to have intermediate lateral restraints at joist locations and are considered fully laterally restrained.

Table 6.3.3c Maximum bearer span (m) — single span — bearer supporting tiled floor and 3 m high non-loadbearing internal wall

Steel section

Effective load width (m)

1.8

2.4

3.0

3.6

4.2

125 TFB

3.9

3.7

3.5

3.4

3.3

180 UB 16.1

5.2

5.0

4.8

4.6

4.4

200 UB 18.2

5.9

5.6

5.4

5.2

5.0

250 UB 25.7

7.7

7.3

7.1

6.8

6.6

250 x 150 x 9 RHS

8.7

8.3

8.0

7.7

7.5

250 x 150 x 5 RHS

7.5

7.1

6.9

6.6

6.1

310 UB 32.0

9.3

8.9

8.5

8.2

8.0

125 x 75 x 2 RHS

2.7

2.4

2.2

2.0

1.9

125 x 75 x 3 RHS

3.2

3.0

2.9

2.7

2.5

150 x 50 x 2 RHS

3.0

2.7

2.4

2.2

2.1

150 x 50 x 3 RHS

3.4

3.3

3.1

2.9

2.7

100 TFB

2.7

2.6

2.5

2.3

2.2

150 PFC

4.8

4.6

4.4

4.2

4.1

180 PFC

5.7

5.4

5.2

5.0

4.9

200 PFC

6.3

6.0

5.8

5.6

5.4

250 PFC

8.3

7.9

7.6

7.3

7.1

300 PFC

9.7

9.2

8.9

8.6

8.3

Table Notes

Load accounted for includes 0.98 kPa permanent floor, 0.92 kN/m permanent wall, permanent member self-weight, 1.5 kPa or 1.1 kN imposed.

Load combinations included are 1.35G and 1.25G+1.5Q for ULS and G + 0.7Q for SLS with a maximum deflection of span/300.

Bearers are assumed to have intermediate lateral restraints at joist locations and are considered fully laterally restrained.

Table 6.3.3d Maximum bearer span (m) — continuous span — bearer supporting tiled floor and 3 m high non-loadbearing internal wall

Steel section

Effective load width (m)

1.8

2.4

3.0

3.6

4.2

125 TFB

4.8

4.3

3.9

3.6

3.3

180 UB 16.1

6.3

5.6

5.1

4.7

4.4

200 UB 18.2

7.2

6.4

5.8

5.3

5.0

250 UB 25.7

9.5

8.5

7.7

7.1

6.6

250 x 150 x 9 RHS

11.6

10.8

9.8

9.1

8.5

250 x 150 x 5 RHS

8.8

7.8

7.1

6.6

6.1

310 UB 32.0

11.5

10.2

9.3

8.5

8.0

125 x 75 x 2 RHS

2.7

2.4

2.2

2.0

1.9

125 x 75 x 3 RHS

3.7

3.3

3.0

2.7

2.5

150 x 50 x 2 RHS

3.1

2.7

2.4

2.2

2.1

150 x 50 x 3 RHS

3.9

3.4

3.1

2.9

2.7

100 TFB

3.2

2.8

2.5

2.3

2.2

150 PFC

6.1

5.4

4.9

4.5

4.2

180 PFC

7.2

6.4

5.8

5.4

5.0

200 PFC

8.0

7.1

6.4

5.9

5.5

250 PFC

10.9

9.7

8.8

8.1

7.6

300 PFC

12.5

11.2

10.1

9.4

8.7

Table Notes

Load accounted for includes 0.98 kPa permanent floor, 0.92 kN/m permanent wall, permanent member self-weight, 1.5 kPa or 1.1 kN imposed.

Load combinations included are 1.35G and 1.25G+1.5Q for ULS and G + 0.7Q for SLS with a maximum deflection of span/300.

Bearers are assumed to have intermediate lateral restraints at joist locations and are considered fully laterally restrained.