6.3.6 Columns

Part 6.3 Structural steel members · NCC 2019: 3.4.4.3

Open 6.3.6 on NCC Online ↗

Structural steel columns must comply with the following:

Columns must support the maximum area provided for in—

Tables 6.3.6a, 6.3.6b and 6.3.6c for columns supporting tiled floor and tiled roof load; and

Tables 6.3.6d, 6.3.6e and 6.3.6f for columns supporting timber floor and metal roof load.

The floor area to be supported is to be determined in accordance with Table 6.3.6g and Figure 6.3.6a.

The flooring system supported by structural steel columns must be fully braced to the footing level either by—

subject to (d), adequately fixing the full height of the column to bracing walls of similar height in the two orthogonal directions of the building; or

a bracing system designed in accordance with AS 1684.2, AS 1684.3, AS/NZS 4600, NASH standard or AS 3700 as appropriate to the materials being used.

For the purposes of (c)(i), the bracing walls must be capable of resisting racking forces in each direction not less than a proportion of the building’s racking force equal to the proportion of floor area that the column is supporting compared to the total floor area of the building.

Acceptable load eccentricity must not exceed 50% of the cross-sectional width plus 100 mm (see Figure 6.3.6b).

Have a minimum nominal yield strength of 250 MPa.

Table 6.3.6a Required column section — columns supporting tiled floor and tiled roof load — roof load area = 0 m2

Column section

Effective height (mm)

Floor load area (m2)

4

10

16

CHS 250

2400

60.3 x 4.5 CHS

88.9 x 5 CHS

114.3 x 4.5 CHS

CHS 250

2700

60.3 x 4.5 CHS

88.9 x 5 CHS

114.3 x 4.5 CHS

CHS 250

3000

60.3 x 4.5 CHS

88.9 x 5 CHS

114.3 x 4.5 CHS

CHS 250

3300

60.3 x 5.4 CHS

88.9 x 5 CHS

114.3 x 5.4 CHS

CHS 250

3600

60.3 x 5.4 CHS

88.9 x 5 CHS

114.3 x 5.4 CHS

CHS 350

2400

60.3 x 2.9 CHS

88.9 x 3.2 CHS

114.3 x 3.2 CHS

CHS 350

2700

60.3 x 2.9 CHS

88.9 x 3.2 CHS

114.3 x 3.2 CHS

CHS 350

3000

60.3 x 2.9 CHS

88.9 x 3.2 CHS

114.3 x 3.2 CHS

CHS 350

3300

76.1 x 2.3 CHS

88.9 x 3.2 CHS

114.3 x 3.2 CHS

CHS 350

3600

76.1 x 2.3 CHS

101.6 x 2.6 CHS

114.3 x 3.2 CHS

SHS 350

2400

65 x 65 x 2 SHS

89 x 89 x 3.5 SHS

100 x 100 x 4 SHS

SHS 350

2700

65 x 65 x 2 SHS

89 x 89 x 3.5 SHS

100 x 100 x 4 SHS

SHS 350

3000

65 x 65 x 2 SHS

89 x 89 x 3.5 SHS

100 x 100 x 4 SHS

SHS 350

3300

65 x 65 x 2 SHS

89 x 89 x 3.5 SHS

100 x 100 x 4 SHS

SHS 350

3600

65 x 65 x 2.5 SHS

89 x 89 x 3.5 SHS

100 x 100 x 4 SHS

SHS 450

2400

50 x 50 x 2 SHS

89 x 89 x 3.5 SHS

100 x 100 x 3 SHS

SHS 450

2700

65 x 65 x 2 SHS

89 x 89 x 3.5 SHS

100 x 100 x 3 SHS

SHS 450

3000

65 x 65 x 2 SHS

89 x 89 x 3.5 SHS

100 x 100 x 3 SHS

SHS 450

3300

65 x 65 x 2 SHS

89 x 89 x 3.5 SHS

100 x 100 x 3 SHS

SHS 450

3600

65 x 65 x 2 SHS

89 x 89 x 3.5 SHS

100 x 100 x 3 SHS

Table Notes

Load accounted for includes 0.98 kPa permanent floor, 1.16 kN/m permanent wall, 0.85 kPa permanent roof, permanent member self-weight, 1.5 kPa or 1.1 kN imposed floor.

Load combinations included are 1.35G and 1.2G + 1.5Q for ULS.

Columns are assumed to be simply-supported at both ends with an effective length factor of 1.

A maximum load eccentricity of 100 mm has been accounted for in the columns.

A roof load area of “0” must be used for columns not supporting roof loads.

The length of wall load allowed for is equal to the square root of the floor area.

Table 6.3.6b Required column section — columns supporting tiled floor and tiled roof load — roof load area = 9 m2

Column section

Effective height (mm)

Floor load area (m2)

4

10

16

CHS 250

2400

76.1 x 4.5 CHS

101.6 x 5 CHS

114.3 x 5.4 CHS

CHS 250

2700

76.1 x 4.5 CHS

101.6 x 5 CHS

114.3 x 5.4 CHS

CHS 250

3000

76.1 x 5.9 CHS

101.6 x 5 CHS

139.7 x 5 CHS

CHS 250

3300

76.1 x 5.9 CHS

101.6 x 5 CHS

139.7 x 5 CHS

CHS 250

3600

76.1 x 5.9 CHS

101.6 x 5 CHS

139.7 x 5 CHS

CHS 350

2400

76.1 x 3.2 CHS

101.6 x 3.2 CHS

139.7 x 3 CHS

CHS 350

2700

76.1 x 3.2 CHS

101.6 x 3.2 CHS

139.7 x 3 CHS

CHS 350

3000

76.1 x 3.2 CHS

114.3 x 3.2 CHS

139.7 x 3 CHS

CHS 350

3300

88.9 x 2.6 CHS

114.3 x 3.2 CHS

139.7 x 3 CHS

CHS 350

3600

88.9 x 2.6 CHS

114.3 x 3.2 CHS

139.7 x 3 CHS

SHS 350

2400

89 x 89 x 3.5 SHS

100 x 100 x 3 SHS

100 x 100 x 4 SHS

SHS 350

2700

89 x 89 x 3.5 SHS

100 x 100 x 3 SHS

100 x 100 x 4 SHS

SHS 350

3000

89 x 89 x 3.5 SHS

100 x 100 x 3 SHS

100 x 100 x 4 SHS

SHS 350

3300

89 x 89 x 3.5 SHS

100 x 100 x 3 SHS

100 x 100 x 4 SHS

SHS 350

3600

89 x 89 x 3.5 SHS

100 x 100 x 3 SHS

100 x 100 x 4 SHS

SHS 450

2400

75 x 75 x 2.5 SHS

89 x 89 x 3.5 SHS

100 x 100 x 3 SHS

SHS 450

2700

75 x 75 x 2.5 SHS

89 x 89 x 3.5 SHS

100 x 100 x 3 SHS

SHS 450

3000

75 x 75 x 2.5 SHS

89 x 89 x 3.5 SHS

100 x 100 x 4 SHS

SHS 450

3300

75 x 75 x 2.5 SHS

89 x 89 x 3.5 SHS

100 x 100 x 4 SHS

SHS 450

3600

75 x 75 x 2.5 SHS

89 x 89 x 3.5 SHS

100 x 100 x 4 SHS

Table Notes

Load accounted for includes 0.98 kPa permanent floor, 1.16 kN/m permanent wall, 0.85 kPa permanent roof, permanent member self-weight, 1.5 kPa or 1.1 kN imposed floor and 0.25 kPa imposed roof.

Load combinations included are 1.35G and 1.2G + 1.5Q for ULS.

Columns are assumed to be simply-supported at both ends with an effective length factor of 1.

A maximum load eccentricity of 100 mm has been accounted for in the columns.

A roof load area of “0” must be used for columns not supporting roof loads.

The length of wall load allowed for is equal to the square root of the floor area.

Table 6.3.6c Required column section — columns supporting tiled floor and tiled roof load — roof load area = 18 m2

Column section

Effective height (mm)

Floor load area (m2)

4

10

16

CHS 250

2400

88.9 x 5 CHS

114.3 x 5.4 CHS

139.7 x 5 CHS

CHS 250

2700

88.9 x 5 CHS

114.3 x 5.4 CHS

139.7 x 5 CHS

CHS 250

3000

88.9 x 5 CHS

114.3 x 5.4 CHS

139.7 x 5 CHS

CHS 250

3300

88.9 x 5.9 CHS

114.3 x 5.4 CHS

139.7 x 5 CHS

CHS 250

3600

88.9 x 5.9 CHS

114.3 x 5.4 CHS

139.7 x 5 CHS

CHS 350

2400

101.6 x 2.6 CHS

114.3 x 3.6 CHS

139.7 x 3.5 CHS

CHS 350

2700

101.6 x 2.6 CHS

114.3 x 3.6 CHS

139.7 x 3.5 CHS

CHS 350

3000

101.6 x 3.2 CHS

114.3 x 3.6 CHS

139.7 x 3.5 CHS

CHS 350

3300

101.6 x 3.2 CHS

114.3 x 3.6 CHS

139.7 x 3.5 CHS

CHS 350

3600

101.6 x 3.2 CHS

114.3 x 3.6 CHS

139.7 x 3.5 CHS

SHS 350

2400

89 x 89 x 3.5 SHS

100 x 100 x 4 SHS

100 x 100 x 4 SHS

SHS 350

2700

89 x 89 x 3.5 SHS

100 x 100 x 4 SHS

100 x 100 x 4 SHS

SHS 350

3000

89 x 89 x 3.5 SHS

100 x 100 x 4 SHS

100 x 100 x 5 SHS

SHS 350

3300

100 x 100 x 3 SHS

100 x 100 x 4 SHS

100 x 100 x 5 SHS

SHS 350

3600

100 x 100 x 3 SHS

100 x 100 x 4 SHS

100 x 100 x 5 SHS

SHS 450

2400

89 x 89 x 3.5 SHS

100 x 100 x 3 SHS

100 x 100 x 4 SHS

SHS 450

2700

89 x 89 x 3.5 SHS

100 x 100 x 3 SHS

100 x 100 x 4 SHS

SHS 450

3000

89 x 89 x 3.5 SHS

100 x 100 x 3 SHS

100 x 100 x 4 SHS

SHS 450

3300

89 x 89 x 3.5 SHS

100 x 100 x 3 SHS

100 x 100 x 4 SHS

SHS 450

3600

89 x 89 x 3.5 SHS

100 x 100 x 3 SHS

100 x 100 x 4 SHS

Table Notes

Load accounted for includes 0.98 kPa permanent floor, 1.16 kN/m permanent wall, 0.85 kPa permanent roof, permanent member self-weight, 1.5 kPa or 1.1 kN imposed floor and 0.25 kPa imposed roof.

Load combinations included are 1.35G and 1.2G + 1.5Q for ULS.

Columns are assumed to be simply-supported at both ends with an effective length factor of 1.

A maximum load eccentricity of 100 mm has been accounted for in the columns.

A roof load area of “0” must be used for columns not supporting roof loads.

The length of wall load allowed for is equal to the square root of the floor area.

Table 6.3.6d Required column section — columns supporting timber floor and metal roof load — roof load area = 0 m2

Column section

Effective height (mm)

Floor load area (m2)

4

10

16

CHS 250

2400

60.3 x 3.6 CHS

76.1 x 5.9 CHS

101.6 x 5 CHS

CHS 250

2700

60.3 x 3.6 CHS

76.1 x 5.9 CHS

101.6 x 5 CHS

CHS 250

3000

60.3 x 4.5 CHS

76.1 x 5.9 CHS

101.6 x 5 CHS

CHS 250

3300

60.3 x 4.5 CHS

76.1 x 5.9 CHS

101.6 x 5 CHS

CHS 250

3600

60.3 x 4.5 CHS

88.9 x 5 CHS

101.6 x 5 CHS

CHS 350

2400

60.3 x 2.3 CHS

88.9 x 2.6 CHS

101.6 x 3.2 CHS

CHS 350

2700

60.3 x 2.9 CHS

88.9 x 2.6 CHS

114.3 x 3.2 CHS

CHS 350

3000

60.3 x 2.9 CHS

88.9 x 3.2 CHS

114.3 x 3.2 CHS

CHS 350

3300

60.3 x 2.9 CHS

88.9 x 3.2 CHS

114.3 x 3.2 CHS

Tables

Same wording in ABCB Housing Provisions 2025. See ABCB Housing Provisions 2025 6.3.6.