7.4.6 Acceptable continuous overflow measure

Part 7.4 Gutters and downpipes · NCC 2019: Table 3.5.3.4a

Open 7.4.6 on NCC Online ↗

(1) For a front face slotted gutter with—

a minimum slot opening area of 1200 mm2 per metre of gutter; and

the lower edge of the slots installed a minimum of 25 mm below the top of the fascia,

the acceptable overflow capacity must be 0.5 L/s/m, constructed in accordance with Figure 7.4.6a.

(2) For a controlled back gap with—

a permanent minimum 10 mm spacer installed between the gutter back and the fascia; and

one spacer per bracket, with the spacer not more than 50 mm wide; and

the back of the gutter installed a minimum of 10 mm below the top of the fascia,

the acceptable overflow capacity must be 1.5 L/s/m, constructed in accordance with Figure 7.4.6b.

(3) For the controlled back gap option, the spacer can be a proprietary clip or bracket that provides the required offset of the gutter from the fascia.

(4) For controlled front bead height with the front bead of the gutter installed a minimum of 10 mm below the top of the fascia, the acceptable overflow capacity is 1.5 L/s/m constructed in accordance with Figure 7.4.6c.

Figure 7.4.6a Construction of front face slotted gutter

Figure 7.4.6b Construction of controlled back gap

Figure 7.4.6c Construction of controlled front bead height

Figure Notes

Front bead of gutter to be a minimum of 10 mm below the top of the fascia.

Same wording in ABCB Housing Provisions 2025. See ABCB Housing Provisions 2025 7.4.6.