Housing Provisions clause · ABCB Housing Provisions 2022

7.4.7 Acceptable dedicated overflow measure per downpipe

Part 7.4 Gutters and downpipes · NCC 2019: Table 3.5.3.4b

Open 7.4.7 on NCC Online ↗

(1) For an end-stop weir with—

a minimum clear width of 100 mm; and

the weir edge installed a minimum 25 mm below the top of the fascia,

the acceptable overflow is 0.5 L/s constructed in accordance with Figure 7.4.7a.

(2) An end-stop weir is not suitable where the end-stop abuts a wall.

(3) For an inverted nozzle installed within 500 mm of a gutter high point with—

a minimum nozzle size of 100 mm × 50 mm positioned lengthways in the gutter; and

the top of the nozzle installed a minimum of 25 mm below the top of the fascia,

the acceptable overflow is 1.2 L/s constructed in accordance with Figure 7.4.7b.

(4) For a front face weir with—

a minimum clear width of 200 mm; and

a minimum clear height of 20 mm; and

the weir edge installed a minimum of 25 mm below the top of the fascia,

the acceptable overflow capacity is 1.0 L/s constructed in accordance with Figure 7.4.7c.

(5) For a rainhead with—

a 75 mm diameter hole in the outward face of the rainhead; and

the centreline of the hole positioned 100 mm below the top of the fascia,

the acceptable overflow capacity is 3.5 L/s constructed in accordance with Figure 7.4.7d.

(6) The rainhead should be detailed to avoid nuisance discharge from the overflow at rainfall intensities below the normal design level.

Figure 7.4.7a Construction of end-stop weir

Figure 7.4.7b Construction of inverted nozzle

Figure 7.4.7c Construction of front face weir

Figure 7.4.7d Construction of rainhead

Same wording in ABCB Housing Provisions 2025. See ABCB Housing Provisions 2025 7.4.7.