8.4.1 Application
(1) Part 8.4 applies subject to the limitations set out in H1D8(1).
(2) Part 8.4 need not be complied with if H1D8(3) is complied with.
(3) The thickness and type of glazing installed in areas of a building that have a high potential for human impact (an area of a building frequented by the occupants during everyday activities in which a person could fall into or against the glazed panel) must comply as follows:
Doors — in accordance with 8.4.2.
Door side panels — in accordance with 8.4.3.
Full height glass panels — in accordance with 8.4.4.
Glazed panels, other than doors or side panels, on the perimeter of rooms — in accordance with 8.4.5.
Bathrooms, ensuite and spa room glazing — in accordance with 8.4.6.
Visibility of glazing — in accordance with 8.4.7.
Identification of safety glass — in accordance with 8.4.8.
Changed in NCC 2025 (minor wording). See ABCB Housing Provisions 2025 8.4.1, or show what changed.
(1) Part 8.4 applies subject to the limitations set out in H1D8(1). (2) Part 8.4 need not be complied with if H1D8(3) H1D8(3)(a) is complied with. (3) The thickness and type of glazing … 8.4.7. Identification of safety glass — in accordance with 8.4.8.
Removed words are struck through; added words are highlighted. Comparison of the text only.
Clauses referred to
- 8.4.2 Doors, side panels and other framed glazed panels
- 8.4.3 Door side panels
- 8.4.4 Full height framed glazed panels
- 8.4.5 Glazed panels, other than doors or side panels, on the perimeter of rooms
- 8.4.6 Kitchen, bathroom, ensuite, spa room and splash-back glazing
- 8.4.7 Visibility of glazing
- 8.4.8 Identification of safety glass