Housing Provisions clause · ABCB Housing Provisions 2022

9.5.4 Installation of smoke alarms

Part 9.5 Smoke alarms and evacuation lighting · NCC 2019: 3.7.5.5

Open 9.5.4 on NCC Online ↗

Smoke alarms required by 9.5.2 and 9.5.3 must be installed on or near the ceiling, in accordance with the following:

Where a smoke alarm is located on the ceiling it must be—

a minimum of 300 mm away from the corner junction of the wall and ceiling; and

between 500 mm and 1500 mm away from the high point and apexes of the ceiling, if the room has a sloping ceiling.

Where (a) is not possible, the smoke alarm may be installed on the wall, and located a minimum of 300 mm and a maximum of 500 mm off the ceiling at the junction with the wall.

Same wording in ABCB Housing Provisions 2025. See ABCB Housing Provisions 2025 9.5.4.