9.5.4 Installation of smoke alarms
Part 9.5 Smoke alarms and evacuation lighting · NCC 2019: 3.7.5.5
Smoke alarms required by 9.5.2 and 9.5.3 must be installed on or near the ceiling, in accordance with the following:
Where a smoke alarm is located on the ceiling it must be—
a minimum of 300 mm away from the corner junction of the wall and ceiling; and
between 500 mm and 1500 mm away from the high point and apexes of the ceiling, if the room has a sloping ceiling.
Where (a) is not possible, the smoke alarm may be installed on the wall, and located a minimum of 300 mm and a maximum of 500 mm off the ceiling at the junction with the wall.
Same wording in ABCB Housing Provisions 2022. See ABCB Housing Provisions 2022 9.5.4.