NT 10.7.2 General installation requirements for walls
NT Part 10.7 Sound insulation · varies 10.7.2 Determination of airborne sound insulation ratings
(1) To achieve an appropriate RW and impact sound resistance, walls must—
be installed in accordance with the appropriate requirements contained in (2) to (6); and
at the junction of sound insulated walls with perimeter walls and roof cladding, be sealed in accordance with any details in Figure NT 10.7.2a.
(2) Masonry units must—
be laid with all joints filled solid, including those between the masonry and any adjoining construction; and
not be chased for services.
(3) Joints between concrete slabs and any adjoining construction must be filed solid.
(4) Plasterboard must be installed as follows:
If one layer is required under this Part, joints must be staggered with the joints in sheets on the opposite face of the wall.
If 2 layers are required, the first layer must be fixed according to (a) and the second layer must be fixed to the first layer with nails, screws or adhesive so that the joints do not coincide with those of the first layer (see Figure NT 10.7.2b).
Joints between sheets or between sheets and any adjoining construction must be taped and filled solid.
Fire-protective grade plasterboard (where nominated) must be the grade manufactured for use in fire-resisting construction.
(5) Steel studs and perimeter members must be installed as follows:
The section of steel must be not less than 0.6 mm thick.
Studs must be not less than 63 mm in depth unless another depth is specified in NT 10.7.1.
Studs must be fixed to steel top and bottom plates of sufficient depth to permit secure fixing of the plasterboard.
All steel members at the perimeter of the wall must be securely fixed to the adjoining structure and be bedded in resilient compound or the joints must be caulked so that there are no voids between the steel members and the wall.
(6) Timber studs and permitter members must be installed as follows:
Studs must be fixed to top and bottom plates of sufficient depth to permit secure fixing of the plasterboard.
Noggings and like members must not bridge between studs supporting different wall leaves.
All timber members at the perimeter of the wall must be securely fixed to the adjoining structure and bedded in resilient compound or the joints must be caulked so that there are no voids between the timber members and the wall.
Insert NT figure (10.7.2a) 10.7.2 as follows:
NT Figure 10.7.2a: Sound insulation between units — double stud wall configuration
Insert NT figure (10.7.2b) 10.7.2 as follows:
NT Figure 10.7.2b: Typical installation of plaster sheets for sound insulation
Changed in NCC 2025. See ABCB Housing Provisions 2025 NT 10.7.2, or show what changed.
Insert NT clause 10.7.2 in clause 10.7.2 as follows: (1) To achieve an appropriate RW and impact sound resistance, … Figure 10.7.2b: Typical installation of plaster sheets for sound insulation
Removed words are struck through; added words are highlighted. Comparison of the text only.