Northern Territory variation · ABCB Housing Provisions 2022

NT 13.7.4 Heating and cooling ductwork

NT Part 13.7 Services · varies 13.7.4 Heating and cooling ductwork

Open on NCC Online ↗

(1) Heating and cooling ductwork and fittings must—

achieve the minimum Total R-Value in accordance with NT Table 13.7.4; and

use thermal insulation material in accordance with AS/NZS 4859.1; and

be sealed against air loss—

by closing all openings in the surface, joints and seams of ductwork with adhesives, mastics, sealants or gaskets in accordance with AS 4254 for a Class C seal; or

for flexible ductwork, with a draw band in conjunction with a sealant or adhesive tape.

(2) Duct insulation located under a suspended floor, in an attached Class 10a building and in a roof space must—

be protected by an outer sleeve of protective sheeting to prevent the insulation becoming damp; and

have the outer protective sleeve sealed with adhesive tape not less than 48 mm wide creating an airtight and waterproof seal.

(3) The requirements of (1) do not apply to heating and cooling ductwork and fittings located within the insulated building envelope including a service riser within the conditioned space, internal floors between storeys and the like.

Insert NT table (13.7.4) 13.7.4 as follows:

NT Table 13.7.4: Heating and cooling ductwork and fittings – minimum total R-Value

Element

Minimum R-Value for ductwork and fittings

| Evaporative cooling system

Heating-only system or refrigerated cooling-only system

Combined heat and refrigerated cooling system

Ductwork

0.6

1.0

1.5

Fittings

0.4

Table Notes

The minimum material R-Value required for ductwork may be reduced by 0.5 for combined heating and refrigerated cooling systems if the ducts are—

under a suspended floor with an enclosed perimeter; or

in a roof space that has an insulation of greater than or equal to R0.5 directly beneath the roofing.

Changed in NCC 2025. See ABCB Housing Provisions 2025 NT 13.7.4, or show what changed.

Insert NT clause 13.7.4 in clause 13.7.4 as follows: (1) Heating and cooling ductwork and fittings must — achieve … greater than or equal to R0.5 directly beneath the roofing.

Removed words are struck through; added words are highlighted. Comparison of the text only.

The national clause