13.7.4 Heating and cooling ductwork
Part 13.7 Services · NCC 2019: 3.12.5.3
(1) Heating and cooling ductwork and fittings must—
achieve the material R-Value in (4); and
be sealed against air loss—
by closing all openings in the surface, joints and seams of ductwork with adhesives, mastics, sealants or gaskets in accordance with AS 4254.1 and AS 4254.2 for a Class C seal; or
for flexible ductwork, with a draw band in conjunction with a sealant or adhesive tape.
(2) Duct insulation must—
abut adjoining duct insulation to form a continuous barrier; and
be installed so that it maintains its position and thickness, other than at flanges and supports; and
where located outside the building, under a suspended floor, in an attached Class 10a building or in a roof space—
be protected by an outer sleeve of protective sheeting to prevent the insulation becoming damp; and
have the outer protective sleeve sealed with adhesive tape not less than 48 mm wide creating an airtight and waterproof seal.
(3) The requirements of (1) do not apply to heating and cooling ductwork and fittings located within the insulated building envelope including a service riser within the conditioned space, internal floors between storeys and the like.
(4) The material R-Value required by (1)(a) must be determined in accordance with the following:
In a heating-only system or cooling-only system including an evaporative cooling system—
ductwork must have a minimum material R-Value of—
in climate zones 1 to 7 — 1.0; and
in climate zone 8 — 1.5; and
fittings must have a minimum material R-Value of 0.4.
In a combined heating and refrigerated cooling system—
ductwork must have a minimum material R-Value of—
in climate zones 1, 3, 4, 6 and 7 — 1.5; and
in climate zones 2 and 5 — 1.0; and
in climate zone 8 — 1.5; and
fittings must have a minimum material R-Value of 0.4.
For the purposes of (b)(i), the minimum material R-Value required for ductwork may be reduced by 0.5 for combined heating and refrigerated cooling systems in climate zones 1, 3, 4, 6 and 7 if the ducts are—
under a suspended floor with an enclosed perimeter; or
in a roof space that has an insulation of greater than or equal to R0.5 directly beneath the roofing.