Table · ABCB Housing Provisions 2022

Table 11.3.6b Continuous wire barrier construction – Maximum permissible deflection of each wire in mm when a 2 kg mass is suspended at mid-span for stainless steel wires

Part 11.3 Barriers and handrails

Open Table 11.3.6b on NCC Online ↗
Wire dia. (mm)Wire spacing (mm)Clear distance between posts (mm)
6009001200150018002000
2.56017119888
807555xx
3.06019138777
80866555
4.06018128877
80864444

Table Notes

Where a change of direction is made in a run of wire, the 2 kg mass must be placed at the middle of the longest span.

If a 3.2 mm diameter wire is used, the deflection figures for a 3.0 mm wire are applied.

This table may also be used for a set of non-continuous (single) vertical wires forming a barrier using the appropriate clear distance between posts as the vertical clear distance between the rails.

The deflection (offset) is measured by hooking a standard spring scale to the mid span of each wire and pulling it horizontally until a force of 19.6 N is applied.

X = not allowed because the required tension would exceed the safe load of the wire.

This table has been limited to 60 mm and 80 mm spaces for 2.5 mm, 3 mm and 4 mm diameter wires because the required wire tensions at greater spacings would require the tension to be beyond the wire safe load limit, or the allowed deflection would be impractical to measure.

Table for 11.3.6 Construction of wire barriers

Same wording in ABCB Housing Provisions 2025. See ABCB Housing Provisions 2025 Table 11.3.6b.