ABCB Housing Provisions 2022
Part 11.3 Barriers and handrails
11 clauses · Open on NCC Online ↗
- 11.3.1 ApplicationCompliance with this Part is achieved by complying with— 11.3.3, 11.3.4 and 11.3.6 for barriers to prevent falls; and 11.3.5 for handrails; and…
- 11.3.2 Explanation of termsFigure 11.3.2 depicts typical stairway and barrier members and associated terminology. (2) Some items have been omitted for clarity. Figure 11.3.2…
- 11.3.3 Barriers to prevent fallsA continuous barrier must be provided along the side of a trafficable surface, such as— a stairway, ramp or the like; and a floor, corridor,…
- 11.3.4 Construction of barriers to prevent fallsA barrier required by 11.3.3 must comply with (2) to (11). (2) The height of a barrier must be in accordance with the following: The height must not…
- 11.3.5 HandrailsHandrails to a stairway or ramp must— be located along at least one side of the stairway flight or ramp; and be located along the full length of the…
- Table 11.3.6a Wire barrier construction – Minimum required tension (N) for stainless steel horizontal wireWire dia. (mm) | Lay | Wire spacing (mm) | Clear distance between posts (mm) 600 | 800 | 900 | 1000 | 1200 | 1500 | 1800 | 2000 | 2500 2.5 | 7x7 |…
- Table 11.3.6b Continuous wire barrier construction – Maximum permissible deflection of each wire in mm when a 2 kg mass is suspended at mid-span for stainless steel wiresWire dia. (mm) | Wire spacing (mm) | Clear distance between posts (mm) 600 | 900 | 1200 | 1500 | 1800 | 2000 2.5 | 60 | 17 | 11 | 9 | 8 | 8 | 8 80 |…
- Table 11.3.6c Continuous wire barrier construction—Minimum required tension (N) for vertical or near-vertical stainless steel wires where the maximum clear spacing between the rails is 900mmWire dia. (mm) | Lay | Wire spacing (mm) | Required tension in Newtons (N) 2.5 | 7 x 19 | 80 | 145 100 | 310 110 | 610 2.5 | 7 x 7 | 80 | 130 100 |…
- 11.3.6 Construction of wire barriersA wire barrier is deemed to meet the requirements of 11.3.4(4) if it is constructed in accordance with (2) to (4). (2) For a horizontal or near…
- 11.3.7 Protection of openable windows – bedroomsA window opening in a bedroom must be provided with protection, where the floor below the window is 2 m or more above the surface beneath. (2) Where…
- 11.3.8 Protection of openable windows – rooms other than bedroomsA window opening in a room other than a bedroom must be provided with protection where the floor below the window is 4 m or more above the surface…