Housing Provisions clause · ABCB Housing Provisions 2022

11.3.6 Construction of wire barriers

Part 11.3 Barriers and handrails · NCC 2019: 3.9.2.5

Open 11.3.6 on NCC Online ↗

(1) A wire barrier is deemed to meet the requirements of 11.3.4(4) if it is constructed in accordance with (2) to (4).

(2) For a horizontal or near horizontal wire system—

when measured with a strain indicator, it must be in accordance with the tension values in Table 11.3.6a; or

when measured for a maximum permissible deflection, it must not exceed the maximum deflections in Table 11.3.6b.

(3) For a non-continuous vertical wire system—

when measured with a strain indicator, it must be in accordance with the tension values in Table 11.3.6a (see Note 4); or

when measured for maximum permissible deflection, it must not exceed the maximum deflections in Table 11.3.6b.

(4) For a continuous vertical or continuous near vertical sloped wire system—

it must have wires of not more than 2.5 mm diameter with a lay of 7 x 7 or 7 x 19 construction; and

changes in direction at support rails must pass around a pulley block without causing permanent deformation to the wire; and

supporting rails must be spaced of not more than 900 mm apart and be of a material that does not allow deflection that would decrease the tension of the wire under load; and

when the wire tension is measured with a strain indicator, it must be in accordance with the tension values in Table 11.3.6c when measured in the furthermost span from the tensioning device.

Table 11.3.6a Wire barrier construction – Minimum required tension (N) for stainless steel horizontal wire

Wire dia. (mm)

Lay

Wire spacing (mm)

Clear distance between posts (mm)

600

800

900

1000

1200

1500

1800

2000

2500

2.5

7x7

60

55

190

263

415

478

823

1080

1139

x

80

382

630

730

824

1025

1288

x

x

x

100

869

1218

1368

x

x

x

x

x

x

2.5

1x19

60

35

218

310

402

585

810

1125

1325

x

80

420

630

735

840

1050

1400

1750

x

x

100

1140

1565

x

x

x

x

x

x

x

3.0

7x7

60

15

178

270

314

506

660

965

1168

1491

80

250

413

500

741

818

1083

1370

1565

x

100

865

1278

1390

1639

x

x

x

x

x

3.0

1x19

60

25

183

261

340

520

790

1025

1180

x

80

325

555

670

785

1025

1330

1725

1980

x

100

1090

1500

1705

1910

x

x

x

x

x

4.0

7x7

60

5

73

97

122

235

440

664

813

1178

80

196

422

480

524

760

1100

1358

1530

2130

100

835

1182

1360

1528

1837

2381

2811

3098

x

4.0

1x19

60

5

5

10

15

20

147

593

890

1280

80

30

192

300

415

593

1105

1303

1435

1844

100

853

1308

1487

1610

2048

2608

3094

3418

3849

4.0

7x19

60

155

290

358

425

599

860

1080

1285

1540

80

394

654

785

915

1143

1485

1860

2105

2615

100

1038

1412

1598

1785

2165

2735

x

x

x

Table Notes

Lay = number of strands by the individual wires in each strand. For example a lay of 7 x 19 consists of 7 strands with 19 individual wires in each strand.

Where a change of direction is made in a run of wire, the tensioning device is to be placed at the end of the longest span.

If a 3.2 mm diameter wire is used, the tension figures for 3.0 mm wire are applied.

This table may also be used for a set of non-continuous (single) vertical wires forming a barrier using the appropriate clear distance between posts as the vertical clear distance between the rails.

X = not allowed because the required tension would exceed the safe load of the wire.

Tension measured with a strain indicator.

Table 11.3.6b Continuous wire barrier construction – Maximum permissible deflection of each wire in mm when a 2 kg mass is suspended at mid-span for stainless steel wires

Wire dia. (mm)

Wire spacing (mm)

Clear distance between posts (mm)

600

900

1200

1500

1800

2000

2.5

60

17

11

9

8

8

8

80

7

5

5

5

x

x

3.0

60

19

13

8

7

7

7

80

8

6

6

5

5

5

4.0

60

18

12

8

8

7

7

80

8

6

4

4

4

4

Table Notes

Where a change of direction is made in a run of wire, the 2 kg mass must be placed at the middle of the longest span.

If a 3.2 mm diameter wire is used, the deflection figures for a 3.0 mm wire are applied.

This table may also be used for a set of non-continuous (single) vertical wires forming a barrier using the appropriate clear distance between posts as the vertical clear distance between the rails.

The deflection (offset) is measured by hooking a standard spring scale to the mid span of each wire and pulling it horizontally until a force of 19.6 N is applied.

X = not allowed because the required tension would exceed the safe load of the wire.

This table has been limited to 60 mm and 80 mm spaces for 2.5 mm, 3 mm and 4 mm diameter wires because the required wire tensions at greater spacings would require the tension to be beyond the wire safe load limit, or the allowed deflection would be impractical to measure.

Table 11.3.6c Continuous wire barrier construction—Minimum required tension (N) for vertical or near-vertical stainless steel wires where the maximum clear spacing between the rails is 900mm

Wire dia. (mm)

Lay

Wire spacing (mm)

Required tension in Newtons (N)

2.5

7 x 19

80

145

100

310

110

610

2.5

7 x 7

80

130

100

280

110

500

Table Notes

Lay = number of strands by the number of individual wires in each strand. For example a lay of 7 x 19 consists of 7 strands with 19 individual wires in each strand.

Vertical wires must have two pulley blocks to each 180 degree change of direction in the wire.

Near vertical wires may only require one pulley block for each change of direction.

Wire tension measured with a strain indicator.

The table only includes 7 x 7 and 7 x 19 wires due to other wires not having sufficient flexibility to make the necessary turns.

Tables

Same wording in ABCB Housing Provisions 2025. See ABCB Housing Provisions 2025 11.3.6.