Table · ABCB Housing Provisions 2022

Table 13.2.3d Pitched roof with horizontal ceiling – minimum R-Value for ceiling insulation: climate zone 3

Part 13.2 Building fabric

Open Table 13.2.3d on NCC Online ↗
Roof ventilationReflective insulation under-roofUnder-roof insulation R-ValueSA ≤ 0.230.23 < SA ≤ 0.320.32 < SA ≤ 0.420.42 < SA ≤ 0.530.53 < SA ≤ 0.64
VentedYes< 0.52.5
≥ 0.5 to < 1.02.0
≥ 1.0 to < 1.52.02.52.52.52.5
≥ 1.5 to < 2.02.02.02.52.52.5
≥ 2.02.52.53.03.03.0
No< 0.53.54.04.55.0X
≥ 0.5 to < 1.03.03.53.54.04.5
≥ 1.0 to < 1.52.53.03.03.03.5
≥ 1.5 to < 2.02.53.03.03.03.0
≥ 2.02.52.53.03.03.0
StandardYes< 0.52.02.02.52.52.5
≥ 0.5 to < 1.02.02.02.52.52.5
≥ 1.0 to < 1.52.02.02.02.02.5
≥ 1.5 to < 2.02.02.52.52.53.0
≥ 2.02.02.02.52.52.5
No< 0.53.54.05.0XX
≥ 0.5 to < 1.03.03.03.54.05.0
≥ 1.0 to < 1.52.52.53.03.03.5
≥ 1.5 to < 2.02.02.02.52.52.5
≥ 2.02.02.02.52.52.5

Table Notes

SA = solar absorptance.

A roof is considered ‘vented’ if it—

has one wind-driven roof ventilator per 50 m2 of ceiling area, with gable, eave or ridge vents; or

has one powered roof ventilator per 200 m2 of ceiling area, with gable, eave or ridge vents; or

is a tiled roof without sarking-type material at roof level.

If a roof is not ‘vented’, it is a ‘standard’ roof.

The R-Value of reflective insulation is not to be included in the R-Value of any under-roof or ceiling insulation.

R-Values listed are for the labelled, declared R-Value of insulation.

X = not permitted.

Table for 13.2.3 Roofs and ceilings

Same wording in ABCB Housing Provisions 2025. See ABCB Housing Provisions 2025 Table 13.2.3d.