13.2.3 Roofs and ceilings
Part 13.2 Building fabric · NCC 2019: NSW 3.12.1.1, 3.12.1.2
(1) Roof and ceiling insulation must achieve the minimum R-Value—
in climate zone 1, in accordance with Tables 13.2.3a, 13.2.3b, 13.2.3j and 13.2.3k as applicable; and
in climate zone 2, in accordance with Tables 13.2.3c and 13.2.3l as applicable; and
in climate zone 3, in accordance with Tables 13.2.3d and 13.2.3m as applicable; and
in climate zone 4, in accordance with Tables 13.2.3e and 13.2.3n as applicable; and
in climate zone 5, in accordance with Tables 13.2.3f and 13.2.3o as applicable; and
in climate zone 6, in accordance with Tables 13.2.3g and 13.2.3p as applicable; and
in climate zone 7, in accordance with Tables 13.2.3h and 13.2.3q as applicable; and
in climate zone 8, in accordance with Tables 13.2.3i and 13.2.3r as applicable.
(2) Reflective insulation installed to comply with (1) must—
have a surface emittance of not more than 0.05; and
be adjacent to a roof space of not less than 20 mm; and
in climate zones 3 to 8, be downward facing.
(3) The thermal bridging in a metal-framed roof must be addressed as follows—
for a pitched roof with a horizontal ceiling—
achieving the Total R-Value in Table 13.2.3s, calculated using a method that accounts for the effects of thermal bridging; or
increasing the R-Value of the insulation between the ceiling frames by R0.5 more than the R-Value derived from (1); or
adding a continuous ceiling insulation layer with a minimum R-Value of R0.13 above or below the ceiling joists or the bottom chords of the trusses; or
achieving the required ceiling R-Value derived from (1) by stacking two layers of insulation immediately on top of each other, such that the top layer is orientated to cover the ceiling joists or bottom chords of the trusses and has an R-Value of at least R0.5; or
for a flat, skillion or cathedral roof—
achieving the Total R-Value in Table 13.2.3t, calculated using a method that accounts for the effects of thermal bridging; or
complying with Table 13.2.3u.
(4) Where 10.8.3(1) of the ABCB Housing Provisions applies, continuous insulation placed above the primary insulation layer to mitigate thermal bridging must have a vapour permeance of not less than that of the primary insulation layer.
(5) Where, for operational or safety reasons, the area of ceiling insulation required is reduced, the loss of insulation must be compensated for in accordance with Table 13.2.3w.
(6) Where the ceiling insulation required by (1) to (5) has an R-Value—
greater than R3.0 and less than or equal to R4.5, it may be reduced to R3.0 within 450 mm of an external wall; or
greater than R4.5, it may be reduced to R3.0 within 450 mm of an external wall, provided all other required ceiling insulation is increased by R0.5.
(7) A roof that—
has metal sheet roofing directly fixed to metal purlins, metal rafters or metal battens; and
does not have a ceiling lining or has a ceiling lining fixed directly to those metal purlins, metal rafters or metal battens,
must have a thermal break, consisting of a material with an R-Value of greater than or equal to 0.2, installed between the metal sheet roofing and its supporting metal purlins, metal rafters or metal battens.
(8) The requirements of (1) to (7) do not apply to roofs constructed using insulated sandwich panels.
(9) Roofs constructed using insulated sandwich panels must achieve the minimum Total R-Value in Table 13.2.3x.
(10) In climate zones 1 to 5, the solar absorptance of the upper surface of a roof must not be more than 0.64.
Table 13.2.3a Pitched roof with horizontal ceiling – minimum R-Value for ceiling insulation: climate zone 1 – single storey dwelling
Roof ventilation
Reflective insulation under-roof
Under-roof insulation R-Value
SA ≤ 0.23
0.23 < SA ≤ 0.32
0.32 < SA ≤ 0.42
0.42 < SA ≤ 0.53
0.53 < SA ≤0 .64
Vented
Yes
< 1.0
1.5
2.0
2.5
3.0
3.5
≥ 1.0 to < 1.5
1.5
1.5
2.0
2.5
3.0
≥ 1.5
1.5
2.0
2.0
2.0
2.0
No
< 1.0
2.5
4.5
X
X
X
≥ 1.0 to < 1.5
2.0
3.0
4.0
5.0
X
≥ 1.5
2.0
2.5
3.0
4.0
5.0
Standard
Yes
< 1.0
1.5
2.0
2.5
4.0
X
≥ 1.0 to < 1.5
1.5
1.5
2.0
3.0
4.0
≥ 1.5
1.5
1.5
2.0
2.5
3.0
No
< 1.0
3.5
X
X
X
X
≥ 1.0 to < 1.5
2.0
3.5
5.5
X
X
≥ 1.5
2.0
2.0
3.5
4.0
6.0
Table Notes
SA = solar absorptance.
A roof is considered ‘vented’ if it—
has one wind-driven roof ventilator per 50 m2 of ceiling area, with gable, eave or ridge vents; or
has one powered roof ventilator per 200 m2 of ceiling area, with gable, eave or ridge vents; or
is a tiled roof without sarking-type material at roof level.
If a roof is not ‘vented’, it is a ‘standard’ roof.
The R-Value of reflective insulation is not to be included in the R-Value of any under-roof or ceiling insulation.
R-Values listed are for the labelled, declared R-Value of insulation.
X = not permitted.
Table 13.2.3b Pitched roof with horizontal ceiling – minimum R-Value for ceiling insulation: climate zone 1 – two (or more) storey dwelling
Roof ventilation
Reflective insulation under-roof
Under-roof insulation R-Value
SA≤ 0.23
0.23< SA≤0.32
0.32< SA≤0.42
0.42< SA≤0.53
0.53< SA≤0.64
Vented
Yes
< 1.0
1.5
1.5
1.5
1.5
2.0
≥ 1.0 to < 1.5
1.5
1.5
1.5
1.5
1.5
≥ 1.5 to < 2.0
1.5
1.5
1.5
1.5
1.5
≥ 2.0
1.5
1.5
1.5
2.0
2.0
No
< 1.0
2.0
2.5
4.0
5.0
X
≥ 1.0 to < 1.5
1.5
1.5
1.5
1.5
2.5
≥ 1.5 to < 2.0
1.5
1.5
1.5
2.0
2.0
≥ 2.0
1.5
1.5
1.5
1.5
1.5
Standard
Yes
< 1.0
1.5
1.5
2.0
3.0
4.0
≥ 1.0 to < 1.5
1.5
1.5
1.5
1.5
2.5
≥ 1.5 to < 2.0
1.5
1.5
1.5
1.5
2.0
≥ 2.0
1.5
1.5
1.5
1.5
1.5
No
< 1.0
2.5
4.0
6.0
X
X
≥ 1.0 to < 1.5
1.5
1.5
1.5
1.5
4.0
≥ 1.5 to < 2.0
1.5
1.5
2.0
2.0
2.5
≥ 2.0
1.5
1.5
1.5
2.0
2.5
Table Notes
SA = solar absorptance.
A roof is considered ‘vented’ if it—
has one wind-driven roof ventilator per 50 m2 of ceiling area, with gable, eave or ridge vents; or
has one powered roof ventilator per 200 m2 of ceiling area, with gable, eave or ridge vents; or
is a tiled roof without sarking-type material at roof level.
If a roof is not ‘vented’, it is a ‘standard’ roof.
The R-Value of reflective insulation is not to be included in the R-Value of any under-roof or ceiling insulation.
R-Values listed are for the labelled, declared R-Value of insulation.
X = not permitted.
Table 13.2.3c Pitched roof with horizontal ceiling – minimum R-Value for ceiling insulation: climate zone 2
Roof ventilation
Reflective insulation under-roof
Under-roof insulation R-Value
SA ≤ 0.23
0.23 < SA ≤ 0.32
0.32 < SA ≤ 0.42
0.42 < SA ≤ 0.64
Vented
Yes
Any
2.5
No
< 0.5
2.5
3.0
3.0
3.5
≥ 0.5
2.5
Standard
Yes
Any
2.5
No
< 0.5
3.0
3.0
3.5
4.0
≥ 0.5 to < 1.0
2.5
2.5
2.5
3.0
≥ 1.0
2.5
Table Notes
SA = solar absorptance.
A roof is considered ‘vented’ if it—
has one wind-driven roof ventilator per 50 m2 of ceiling area, with gable, eave or ridge vents; or
has one powered roof ventilator per 200 m2 of ceiling area, with gable, eave or ridge vents; or
is a tiled roof without sarking-type material at roof level.
If a roof is not ‘vented’, it is a ‘standard’ roof.
The R-Value of reflective insulation is not to be included in the R-Value of any under roof or ceiling insulation.
R-Values listed are for the labelled, declared R-Value of insulation.
Table 13.2.3d Pitched roof with horizontal ceiling – minimum R-Value for ceiling insulation: climate zone 3
Roof ventilation
Reflective insulation under-roof
Under-roof insulation R-Value
SA ≤ 0.23
0.23 < SA ≤ 0.32
0.32 < SA ≤ 0.42
0.42 < SA ≤ 0.53
0.53 < SA ≤ 0.64
Vented
Yes
< 0.5
2.5
≥ 0.5 to < 1.0
2.0
≥ 1.0 to < 1.5
2.0
2.5
2.5
2.5
2.5
≥ 1.5 to < 2.0
2.0
2.0
2.5
2.5
2.5
≥ 2.0
2.5
2.5
3.0
3.0
3.0
No
< 0.5
3.5
4.0
4.5
5.0
X
≥ 0.5 to < 1.0
3.0
3.5
3.5
4.0
4.5
≥ 1.0 to < 1.5
2.5
3.0
3.0
3.0
3.5
≥ 1.5 to < 2.0
2.5
3.0
3.0
3.0
3.0
≥ 2.0
2.5
2.5
3.0
3.0
3.0
Standard
Yes
< 0.5
2.0
2.0
2.5
2.5
2.5
≥ 0.5 to < 1.0
2.0
2.0
2.5
2.5
2.5
≥ 1.0 to < 1.5
2.0
2.0
2.0
2.0
2.5
≥ 1.5 to < 2.0
2.0
2.5
2.5
2.5
3.0
≥ 2.0
2.0
2.0
2.5
2.5
2.5
No
< 0.5
3.5
4.0
5.0
X
X
≥ 0.5 to < 1.0
3.0
3.0
3.5
4.0
5.0
≥ 1.0 to < 1.5
2.5
2.5
3.0
3.0
3.5
≥ 1.5 to < 2.0
2.0
2.0
2.5
2.5
2.5
≥ 2.0
2.0
2.0
2.5
2.5
2.5
Table Notes
SA = solar absorptance.
A roof is considered ‘vented’ if it—
has
Tables
- Table 13.2.3a Pitched roof with horizontal ceiling – minimum R-Value for ceiling insulation: climate zone 1 – single storey dwelling
- Table 13.2.3b Pitched roof with horizontal ceiling – minimum R-Value for ceiling insulation: climate zone 1 – two (or more) storey dwelling
- Table 13.2.3c Pitched roof with horizontal ceiling – minimum R-Value for ceiling insulation: climate zone 2
- Table 13.2.3d Pitched roof with horizontal ceiling – minimum R-Value for ceiling insulation: climate zone 3
- Table 13.2.3e Pitched roof with horizontal ceiling – minimum R-Value for ceiling insulation: climate zone 4
- Table 13.2.3f Pitched roof with horizontal ceiling – minimum R-Value for ceiling insulation: climate zone 5
- Table 13.2.3g Pitched roof with horizontal ceiling – minimum R-Value for ceiling insulation: climate zone 6
- Table 13.2.3h Pitched roof with horizontal ceiling – minimum R-Value for ceiling insulation: climate zone 7
- Table 13.2.3i Pitched roof with horizontal ceiling – minimum R-Value for ceiling insulation: climate zone 8
- Table 13.2.3j Flat, skillion or cathedral roof – minimum R-Value for ceiling insulation: climate zone 1 – single storey dwelling
- Table 13.2.3k Flat, skillion or cathedral roof – minimum R-Value for ceiling insulation: climate zone 1 – two (or more) storey dwelling
- Table 13.2.3l Flat, skillion or cathedral roof – minimum R-Value for ceiling insulation: climate zone 2
- Table 13.2.3m Flat, skillion or cathedral roof – minimum R-Value for ceiling insulation: climate zone 3
- Table 13.2.3n Flat, skillion or cathedral roof – minimum R-Value for ceiling insulation: climate zone 4
- Table 13.2.3o Flat, skillion or cathedral roof – minimum R-Value for ceiling insulation: climate zone 5
- Table 13.2.3p Flat, skillion or cathedral roof – minimum R-Value for ceiling insulation: climate zone 6
- Table 13.2.3q Flat, skillion or cathedral roof – minimum R-Value for ceiling insulation: climate zone 7
- Table 13.2.3r Flat, skillion or cathedral roof – minimum R-Value for ceiling insulation: climate zone 8
- Table 13.2.3s Metal-framed pitched roof with horizontal ceiling – minimum Total R-Value of ceiling to account for thermal bridging
- Table 13.2.3t Metal-framed flat, skillion or cathedral roof – minimum Total R-Value to account for thermal bridging
- Table 13.2.3u Metal-framed flat, skillion or cathedral roof – thermal bridging mitigation
- Table 13.2.3v Direction of heat flow
- Table 13.2.3w Adjusted minimum R-Value of ceiling insulation required to compensate for loss of ceiling insulation area
- Table 13.2.3x Total R-Value for roofs constructed with insulated sandwich panels
Changed in NCC 2025. See ABCB Housing Provisions 2025 13.2.3, or show what changed.
(1) Roof and ceiling insulation must achieve the minimum R-Value … fixed directly to those metal purlins, metal rafters or metal battens, battens must have a thermal break, consisting of a material with … absorptance. A roof is considered ‘vented’ if it — has
Removed words are struck through; added words are highlighted. Comparison of the text only.
State and territory variations all clauses side by side →
- NSW Replaced Delete clause 13.2.3 and insert NSW 13.2.3 as follows: (1) A roof that— has metal sheet roofing directly fixed to metal purlins,…
- NT Varied A roof must achieve the Total R-Value of 2.7 for the downwards direction of heat flow in climate zone 1 and downwards and…