Table · ABCB Housing Provisions 2022

Table 13.2.3g Pitched roof with horizontal ceiling – minimum R-Value for ceiling insulation: climate zone 6

Part 13.2 Building fabric

Open Table 13.2.3g on NCC Online ↗
Roof ventilationReflective insulation under-roofUnder-roof insulation R-Value0.23 ≤ SA ≤ 0.640.64 < SA ≤ 0.96
VentedYes< 1.04.03.5
≥ 1.03.5
No< 1.04.0
≥ 1.03.5
StandardYes< 1.03.5
≥ 1.03.0
No< 1.04.0
≥ 1.03.5

Table Notes

SA = solar absorptance.

A roof is considered ‘vented’ if it—

has one wind-driven roof ventilator per 50 m2 of ceiling area, with gable, eave or ridge vents; or

has one powered roof ventilator per 200 m2 of ceiling area, with gable, eave or ridge vents; or

is ventilated to outdoor air through evenly distributed openings with Table 10.8.3; or

is a tiled roof without sarking-type material at roof level.

If a roof is not ‘vented’, it is a ‘standard’ roof.

In climate zones 6, 7 and 8, roof ventilation must comply with 10.8.3.

The R-Value of reflective insulation is not to be included in the R-Value of any under-roof or ceiling insulation.

R-Values listed are for the labelled, declared R-Value of insulation.

Table for 13.2.3 Roofs and ceilings

Same wording in ABCB Housing Provisions 2025. See ABCB Housing Provisions 2025 Table 13.2.3g.