Table · ABCB Housing Provisions 2022
Table 13.2.3u Metal-framed flat, skillion or cathedral roof – thermal bridging mitigation
| Minimum ceiling insulation R-Value from Tables 13.2.3j to 13.2.3r | Option 1 – increase insulation between roof frame members to specified minimum R-Value | Option 2 – add a layer of continuous insulation with specified minimum R-Value above or below the roof frame members |
|---|---|---|
| 1.0 | 1.5 | 0.13 |
| 1.5 | 2.5 | 0.30 |
| 2.0 | 3.5 | 0.30 |
| 2.5 | 5.0 | 0.40 |
| 3.0 | 6.0 | 0.60 |
| 3.5 | X | 0.60 |
| 4.0 | X | 0.60 |
| 4.5 | X | 0.60 |
| 5.0 | X | 0.60 |
| 5.5 | X | 0.60 |
| 6.0 | X | 0.60 |
Table Notes
Minimum R-Values are in-situ values. They account for compression of insulation.
X = not permitted.
Table for 13.2.3 Roofs and ceilings
Same wording in ABCB Housing Provisions 2025. See ABCB Housing Provisions 2025 Table 13.2.3u.