Table · ABCB Housing Provisions 2022

Table 13.2.5g Masonry veneer wall – minimum insulation R-Value: climate zone 4

Part 13.2 Building fabric

Open Table 13.2.5g on NCC Online ↗
SAOverhang (mm)Wall height (m)
≤ 2.4> 2.4 to ≤ 2.7> 2.7 to ≤ 3.0> 3.0 to ≤ 3.6
≤ 0.3502.02.52.5X
> 0 to ≤ 3002.02.02.5X
> 300 to ≤ 4502.02.02.53.0
> 450 to ≤ 6002.02.52.53.0
> 600 to ≤ 9002.52.52.53.0
> 900 to ≤ 1200X3.03.03.0
> 1200 to ≤ 1500XX3.0X
> 0.35 to ≤ 0.502.02.52.5X
> 0 to ≤ 3002.02.02.5X
> 300 to ≤ 4502.02.02.53.0
> 450 to ≤ 6002.02.02.53.0
> 600 to ≤ 9002.52.52.53.0
> 900 to ≤ 1200X2.52.53.0
> 1200 to ≤ 1500XX3.03.0
> 0.5 to ≤ 0.702.02.52.5X
> 0 to ≤ 3002.02.02.5X
> 300 to ≤ 4502.02.02.53.0
> 450 to ≤ 6002.02.02.53.0
> 600 to ≤ 9002.02.02.53.0
> 900 to ≤ 12003.02.52.53.0
> 1200 to ≤ 1500X3.02.53.0

Table Notes

SA = solar absorptance.

R-Values listed are for the labelled, declared R-Value of insulation.

X = not permitted.

This Table shows wall heights for single storey dwellings. For two storey (or more) dwellings, add R0.5 to the R-Values given in this Table.

Table for 13.2.5 External walls

Changed in NCC 2025. See ABCB Housing Provisions 2025 Table 13.2.5g, or show what changed.

SA | Overhang (mm) | Wall height (m) ≤ 2.4 … dwellings, add R0.5 to the R-Values given in this Table. Where an overhang of > 1500 mm is used, the values for > 1200 to ≤ 1500 apply provided no more than 15% of the total opaque wall area of the dwelling (excluding windows/doors) is covered by overhangs > 1500 mm.

Removed words are struck through; added words are highlighted. Comparison of the text only.

Defined terms used