Table · ABCB Housing Provisions 2022

Table 13.2.5h Masonry cavity wall – minimum insulation R-Value: climate zone 4

Part 13.2 Building fabric

Open Table 13.2.5h on NCC Online ↗
SAOverhang (mm)Wall height (m)
≤ 2.4> 2.4 to ≤ 2.7> 2.7 to ≤ 3.0> 3.0 to ≤ 3.6
≤ 0.3500.250.250.510.75
> 0 to ≤ 3000.510.510.510.75
> 300 to ≤ 4500.510.510,510.75
> 450 to ≤ 6000.510.510.510.75
> 600 to ≤ 9001.080.750.751.08
> 900 to ≤ 12001.441.081.081.08
> 1200 to ≤ 1500X1.441.441.08
> 1500 to ≤ 1800XXX1.44
> 0.35 to ≤ 0.500.250.250.510.62
> 0 to ≤ 3000.250.250.510.62
> 300 to ≤ 4500.510.510.510.62
> 450 to ≤ 6000.510.510.510.75
> 600 to ≤ 9000.750.620.620.75
> 900 to ≤ 12001.081.080.751.08
> 1200 to ≤ 1500X1.441.081.08
> 1500 to ≤ 1800XX1.441.44
> 0.5 to ≤ 0.700.00.250.250.51
> 0 to ≤ 3000.250.250.250.51
> 300 to ≤ 4500.250.250.510.51
> 450 to ≤ 6000.250.250.510.51
> 600 to ≤ 9000.250.510.510.62
> 900 to ≤ 12000.510.620.620.75
> 1200 to ≤ 15001.081.081.081.08
> 1500 to ≤ 18001.441.441.081.08

Table Notes

SA = solar absorptance.

R-Values listed are for the labelled, declared R-Value of insulation.

X = not permitted.

This Table shows wall heights for single storey dwellings. For two storey (or more) dwellings, add R0.25 to the R-Values given in this Table.

Table for 13.2.5 External walls

Changed in NCC 2025. See ABCB Housing Provisions 2025 Table 13.2.5h, or show what changed.

SA | Overhang (mm) | Wall height (m) ≤ 2.4 … dwellings, add R0.25 to the R-Values given in this Table. Where an overhang of > 1800 mm is used, the values for > 1500 to ≤ 1800 apply provided no more than 15% of the total opaque wall area of the dwelling (excluding windows/doors) is covered by overhangs > 1800 mm.

Removed words are struck through; added words are highlighted. Comparison of the text only.

Defined terms used