Table · ABCB Housing Provisions 2022
Table 6.2.1a Subfloor openings
| Climatic zone (see Figure 6.2.1a) | Minimum aggregate subfloor ventilation openings with no membrane (mm2/m of wall) | Minimum aggregate subfloor ventilation openings with ground sealed with impervious membrane (mm2/m of wall) |
|---|---|---|
| A | 2000 | 1000 |
| B | 4000 | 2000 |
| C | 6000 | 3000 |
Table Notes
In situations where openings in external walls and internal subfloor walls, including separating walls, are not able to be provided, additional measures must be provided to ensure that the overall level of ventilation of the subfloor space is maintained. This may include measures similar to those in 6.2.1(5) i.e. providing durability class timbers, or having the ground sealed in the subfloor space with an impervious membrane.
Table for 6.2.1 Subfloor ventilation
Same wording in ABCB Housing Provisions 2025. See ABCB Housing Provisions 2025 Table 6.2.1a.