Table · ABCB Housing Provisions 2025

Table 6.2.1a Subfloor openings

Part 6.2 Subfloor ventilation

Open Table 6.2.1a on NCC Online ↗
Climatic zone (see Figure 6.2.1a)Minimum aggregate subfloor ventilation openings with no membrane (mm2/m of wall)Minimum aggregate subfloor ventilation openings with ground sealed with impervious membrane (mm2/m of wall)
A20001000
B40002000
C60003000

Table Notes

In situations where openings in external walls and internal subfloor walls, including separating walls, are not able to be provided, additional measures must be provided to ensure that the overall level of ventilation of the subfloor space is maintained. This may include measures similar to those in 6.2.1(5) i.e. providing durability class timbers, or having the ground sealed in the subfloor space with an impervious membrane.

Table for 6.2.1 Subfloor ventilation

Same wording in ABCB Housing Provisions 2022. See ABCB Housing Provisions 2022 Table 6.2.1a.