Table · ABCB Housing Provisions 2022
Table 6.3.5a Maximum lintel span — lintel supporting metal sheet roof, timber floor and 3 m high exterior wall — roof load width = 1.5 m
Part 6.3 Structural steel members
| Section | Floor load width (m) | ||
|---|---|---|---|
| 0 | 1.8 | 3.6 | |
| 150 UB 14.0 | 4.4 | 3.0 | 2.5 |
| 200 UB 25.4 | 6.8 | 4.7 | 4.0 |
| 250 UB 31.4 | 7.7 | 5.3 | 4.6 |
| 100 TFB | 2.8 | 1.8 | 1.5 |
| 150 PFC | 5.7 | 3.8 | 3.2 |
| 200 PFC | 6.5 | 4.3 | 3.7 |
| 250 PFC | 8.4 | 5.7 | 4.9 |
| 75 x 75 x 5 EA | 2.0 | 1.0 | – |
| 90 x 90 x 6 EA | 3.0 | 1.5 | 1.0 |
| 100 x 100 x 6 EA | 3.0 | 1.8 | 1.0 |
| 125 x 75 x 6 UA | 3.0 | 1.8 | 1.3 |
| 150 x 100 x 10 UA | 4.0 | 3.0 | 2.5 |
Table Notes
Load accounted for includes 0.53 kPa permanent floor, 1.16 kN/m permanent wall, 0.4 kPa permanent roof, permanent member self-weight, 1.5 kPa or 1.1 kN imposed floor, positive roof wind pressure of 0.95 kPa and negative roof wind pressure of -1.49 kPa.
Load combinations included are 1.35G and 1.2G + 1.5Q, 1.2G + WU + 0.4Q, 0.9G + WU for ULS and G + 0.7Q, G + WS.
0.9G + WS for SLS with a maximum deflection of span/300.
Lintels are assumed to be partially restrained at both ends with no rotational restraint and are designed as members without full lateral restraint.
A floor load of “0” must be used for lintels not supporting floor loads.
Table for 6.3.5 Lintels
Same wording in ABCB Housing Provisions 2025. See ABCB Housing Provisions 2025 Table 6.3.5a.