Table · ABCB Housing Provisions 2022
Table 6.3.6f Required column section — columns supporting timber floor and metal roof load — roof load area = 18 m2
Part 6.3 Structural steel members
| Column section | Effective height (mm) | Floor load area (m2) | ||
|---|---|---|---|---|
| 4 | 10 | 16 | ||
| CHS 250 | 2400 | 76.1 x 4.5 CHS | 101.6 x 5 CHS | 114.3 x 5.4 CHS |
| CHS 250 | 2700 | 76.1 x 5.9 CHS | 101.6 x 5 CHS | 114.3 x 5.4 CHS |
| CHS 250 | 3000 | 76.1 x 5.9 CHS | 101.6 x 5 CHS | 114.3 x 5.4 CHS |
| CHS 250 | 3300 | 76.1 x 5.9 CHS | 101.6 x 5 CHS | 114.3 x 5.4 CHS |
| CHS 250 | 3600 | 76.1 x 5.9 CHS | 101.6 x 5 CHS | 114.3 x 5.4 CHS |
| CHS 350 | 2400 | 76.1 x 3.2 CHS | 101.6 x 3.2 CHS | 114.3 x 3.6 CHS |
| CHS 350 | 2700 | 76.1 x 3.2 CHS | 101.6 x 3.2 CHS | 114.3 x 3.6 CHS |
| CHS 350 | 3000 | 88.9 x 2.6 CHS | 101.6 x 3.2 CHS | 114.3 x 3.6 CHS |
| CHS 350 | 3300 | 88.9 x 2.6 CHS | 101.6 x 3.2 CHS | 114.3 x 3.6 CHS |
| CHS 350 | 3600 | 88.9 x 2.6 CHS | 101.6 x 3.2 CHS | 114.3 x 3.6 CHS |
| SHS 350 | 2400 | 89 x 89 x 3.5 SHS | 100 x 100 x 3 SHS | 100 x 100 x 4 SHS |
| SHS 350 | 2700 | 89 x 89 x 3.5 SHS | 100 x 100 x 3 SHS | 100 x 100 x 4 SHS |
| SHS 350 | 3000 | 89 x 89 x 3.5 SHS | 100 x 100 x 3 SHS | 100 x 100 x 4 SHS |
| SHS 350 | 3300 | 89 x 89 x 3.5 SHS | 100 x 100 x 3 SHS | 100 x 100 x 4 SHS |
| SHS 350 | 3600 | 89 x 89 x 3.5 SHS | 100 x 100 x 3 SHS | 100 x 100 x 4 SHS |
| SHS 450 | 2400 | 75 x 75 x 2.5 SHS | 89 x 89 x 3.5 SHS | 100 x 100 x 3 SHS |
| SHS 450 | 2700 | 75 x 75 x 2.5 SHS | 89 x 89 x 3.5 SHS | 100 x 100 x 3 SHS |
| SHS 450 | 3000 | 75 x 75 x 2.5 SHS | 89 x 89 x 3.5 SHS | 100 x 100 x 3 SHS |
| SHS 450 | 3300 | 75 x 75 x 2.5 SHS | 89 x 89 x 3.5 SHS | 100 x 100 x 3 SHS |
| SHS 450 | 3600 | 75 x 75 x 2.5 SHS | 89 x 89 x 3.5 SHS | 100 x 100 x 3 SHS |
Table Notes
Load accounted for includes 0.53 kPa permanent floor, 1.16 kN/m permanent wall, 0.4 kPa permanent roof, permanent member self-weight, 1.5 kPa or 1.1 kN imposed floor and 0.25 kPa imposed roof.
Load combinations included are 1.35G and 1.2G + 1.5Q for ULS.
Columns are assumed to be simply-supported at both ends with an effective length factor of 1.
A maximum load eccentricity of 100 mm has been accounted for in the columns.
A roof load area of “0” must be used for columns not supporting roof loads.
The length of wall load allowed for is equal to the square root of the floor area.
Table for 6.3.6 Columns
Same wording in ABCB Housing Provisions 2025. See ABCB Housing Provisions 2025 Table 6.3.6f.