Verification Method · NCC 2025 Volume One
C1V1 Fire spread between buildings on adjoining allotments
Part C1 Fire resistance · NCC 2019: CV1
Compliance with C1P2(1)(c) to avoid the spread of fire between buildings on adjoining allotments is verified when it is calculated that—
a building will not cause heat flux in excess of those set out in Column 2 of Table C1V1 at the location on an adjoining property set out in Column 1 of Table C1V1; and
when located at the distances from the allotment boundary set out in Column 1 of Table C1V1, a building is capable of withstanding the heat flux set out in Column 2 of Table C1V1 without ignition.
Table C1V1 Fire spread between buildings on adjoining allotments
Column 1 (Location)
Column 2 (Heat flux (kW/m2))
On boundary
80
1 m from boundary
40
3 m from boundary
20
6 m from boundary
10
Tables
Same wording in NCC 2022 Volume One. See NCC 2022 Volume One C1V1.