C2D13 Fire-protected timber: Concession
Part C2 Fire resistance and stability · NCC 2019: C1.13
Fire-protected timber may be used wherever an element is required to be non-combustible, provided—
the building is—
a separate building; or
a part of a building—
which only occupies part of a storey, and is separated from the remaining part by a fire wall; or
which is located above or below a part not containing fire-protected timber and the floor between the adjoining parts is provided with an FRL not less than that prescribed for a fire wall for the lower storey; and
the building has an effective height of not more than 25 m; and
the building has a sprinkler system (other than a FPAA101D or FPAA101H system) throughout complying with Specification 17; and
any insulation installed in the cavity of the timber building element to have an FRL is non-combustible; and
cavity barriers are provided in accordance with Specification 9.