Deemed-to-Satisfy Provision · NCC 2022 Volume One

C2D14 Ancillary elements

Part C2 Fire resistance and stability · NCC 2019: C1.14

Open C2D14 on NCC Online ↗

An ancillary element must not be fixed, installed, attached to or supported by the concealed internal parts or external face of an external wall that is required to be non-combustible unless it is one of the following:

An ancillary element that is non-combustible.

A gutter, downpipe or other plumbing fixture or fitting.

A flashing.

A grate, grille or similar cover not more than 2 m2 in area associated with a building service.

An electrical switch, socket-outlet, cover plate or the like.

A light fitting.

A required sign.

A sign other than one provided under (a) or (g) that—

achieves a group number of 1 or 2; and

does not extend beyond one storey; and

does not extend beyond one fire compartment; and

is separated vertically from other signs permitted under (h) by at least 2 storeys.

An awning, sunshade, canopy, blind or shading hood other than one provided under (a) that—

meets the relevant requirements of Table S7C7 as for an internal element; and

serves a storey—

at ground level; or

immediately above a storey at ground level; and

does not serve an exit, where it would render the exit unusable in a fire.

A part of a security, intercom or announcement system.

Wiring.

Waterproofing material installed in accordance with AS 4654.2 and applied to an adjacent floor surface, including vertical upturn, or a roof surface.

Collars, sleeves and insulation associated with service installations.

Screens applied to vents, weepholes and gaps complying with AS 3959.

Wiper and brush seals associated with doors, windows or other openings.

A gasket, caulking, sealant or adhesive directly associated with (a) to (o).

Limitations

C2D14 does not apply to ancillary elements fixed, installed or attached to the internal face or lining of an external wall.

Notes

C2D14 does not prevent the mounting of domestic air-conditioning condenser units on external walls.

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One C2D14.
Can't meet C2D14? A Performance Solution must meet the Performance Requirements it satisfies: C1P1, C1P2, C1P3, C1P4, C1P5, C1P6, C1P7, C1P8, C1P9. Start a Performance Solution →