Deemed-to-Satisfy Provision · NCC 2022 Volume One
C2D2 Type of construction required
Part C2 Fire resistance and stability · NCC 2019: C1.1
Varied in SA. Check the variation for your state.
(1) The minimum Type of fire-resisting construction of a building must be determined in accordance with Table C2D2, except as allowed for—
certain Class 2, 3 or 9c buildings, in C2D6; and
a Class 4 part of a building located on the top storey, in C2D4(2); and
open spectator stands and indoor sports stadiums, in C2D8.
(2) Each building element must comply with Specification 5 as applicable.
Table C2D2 Type of construction required
Rise in storeys
Class of building 2, 3, 9
Class of building 5, 6, 7, 8
4 or more
A
A
3
A
B
2
B
C
1
C
C
Tables
Same wording in NCC 2025 Volume One. See NCC 2025 Volume One C2D2.
Can't meet C2D2? A Performance Solution must meet the Performance Requirements it satisfies: C1P1, C1P2, C1P3, C1P4, C1P5, C1P6, C1P7, C1P8, C1P9. Start a Performance Solution →
State and territory variations all clauses side by side →
Clauses referred to
- C2D6 Two storey Class 2, 3 or 9c buildings
- C2D4 Buildings of multiple classification
- C2D8 Open spectator stands and indoor sports stadiums