Deemed-to-Satisfy Provision · NCC 2022 Volume One

C2D2 Type of construction required

Part C2 Fire resistance and stability · NCC 2019: C1.1

Open C2D2 on NCC Online ↗
Varied in SA. Check the variation for your state.

(1) The minimum Type of fire-resisting construction of a building must be determined in accordance with Table C2D2, except as allowed for—

certain Class 2, 3 or 9c buildings, in C2D6; and

a Class 4 part of a building located on the top storey, in C2D4(2); and

open spectator stands and indoor sports stadiums, in C2D8.

(2) Each building element must comply with Specification 5 as applicable.

Table C2D2 Type of construction required

Rise in storeys

Class of building 2, 3, 9

Class of building 5, 6, 7, 8

4 or more

A

A

3

A

B

2

B

C

1

C

C

Tables

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One C2D2.
Can't meet C2D2? A Performance Solution must meet the Performance Requirements it satisfies: C1P1, C1P2, C1P3, C1P4, C1P5, C1P6, C1P7, C1P8, C1P9. Start a Performance Solution →

State and territory variations all clauses side by side →