Deemed-to-Satisfy Provision · NCC 2022 Volume One

C3D14 Electricity supply system

Part C3 Compartmentation and separation · NCC 2019: C2.13

Open C3D14 on NCC Online ↗

(1) An electricity substation located within a building must—

be separated from any other part of the building by construction having an FRL of not less than 120/120/120; and

have any doorway in that construction protected with a self-closing fire door having an FRL of not less than –/120/30.

(2) A main switchboard located within the building which sustains emergency equipment operating in the emergency mode must—

be separated from any other part of the building by construction having an FRL of not less than 120/120/120; and

have any doorway in that construction protected with a self-closing fire door having an FRL of not less than –/120/30.

(3) Subject to (4), electrical conductors must—

have a classification in accordance with AS/NZS 3013 of not less than—

if located in a position that could be subject to damage by motor vehicles — WS53W; or

otherwise — WS52W; or

be enclosed or otherwise protected by construction having an FRL of not less than 120/120/120.

(4) The requirements of (3) only apply to electrical conductors located within a building that supply—

a substation located within the building which supplies a main switchboard covered by (2); or

a main switchboard covered by (2).

(5) Where emergency equipment is required in a building, all switchboards in the electrical installation, which sustain the electricity supply to the emergency equipment, must be constructed so that emergency equipment switchgear is separated from non-emergency equipment switchgear by metal partitions designed to minimise the spread of a fault from the non-emergency equipment switchgear.

(6) For the purposes of (5), emergency equipment includes but is not limited to the following:

Fire hydrant booster pumps.

Pumps for automatic sprinkler systems, water spray, chemical fluid suppression systems or the like.

Pumps for fire hose reels where such pumps and fire hose reels form the sole means of fire protection in the building.

Air handling systems designed to exhaust and control the spread of fire and smoke.

Emergency lifts.

Control and indicating equipment.

Emergency warning and intercom systems.