Deemed-to-Satisfy Provision · NCC 2022 Volume One
C3D15 Public corridors in Class 2 and 3 buildings
Part C3 Compartmentation and separation · NCC 2019: C2.14
In a Class 2 or 3 building, a public corridor, if more than 40 m in length, must be divided at intervals of not more than 40 m with smoke-proof walls complying with S11C2.
Same wording in NCC 2025 Volume One. See NCC 2025 Volume One C3D15.
Can't meet C3D15? A Performance Solution must meet the Performance Requirements it satisfies: C1P1, C1P2, C1P3, C1P4, C1P5, C1P6, C1P7, C1P8, C1P9. Start a Performance Solution →