Specification clause · NCC 2022 Volume One

S11C2 Class 9a health-care buildings

Specification 11 Smoke-proof walls in health-care and residential care buildings · NCC 2019: Spec C2.5: 2

Open S11C2 on NCC Online ↗

Smoke-proof walls required by C3D6 in Class 9a health-care buildings must comply with the following:

Be non-combustible and extend to the underside of—

the floor above; or

a non-combustible roof covering; or

a ceiling having a resistance to the incipient spread of fire to the space above itself of not less than 60 minutes.

Not incorporate any glazed areas unless the glass is safety glass as defined in AS 1288.

Only have doorways which are fitted with smoke doors complying with Specification 12.

Have all openings around penetrations and the junctions of the smoke-proof wall and the remainder of the building stopped with non-combustible material to prevent the free passage of smoke.

Incorporate smoke dampers where air-handling ducts penetrate the wall unless the duct forms part of a smoke hazard management system required to continue air movement through the duct during a fire.

Changed in NCC 2025. See NCC 2025 Volume One S11C2, or show what changed.

Smoke-proof walls required by C3D6 in Class 9a health-care buildings must comply with the following: Be lined on both sides. Be non-combustible and extend to the underside of — the … the space above itself of not less than 60 minutes. If plasterboard is used as the lining on a wall, it must be minimum of 13 mm thick plasterboard. Not incorporate any glazed areas unless the glass is safety … to prevent the free passage of smoke. Incorporate smoke dampers complying with AS 1668.1 where air-handling ducts penetrate the wall unless the duct forms … to continue air movement through the duct during a fire.