Deemed-to-Satisfy Provision · NCC 2022 Volume One

C4D12 Bounding construction: Class 2 and 3 buildings and Class 4 parts

Part C4 Protection of openings · NCC 2019: C3.11

Open C4D12 on NCC Online ↗
Varied in NSW. Check the variation for your state.

(1) A doorway in a Class 2 or 3 building must be protected if it provides access from a sole-occupancy unit to—

a public corridor, public lobby, or the like; or

a room not within a sole-occupancy unit; or

the landing of an internal non fire-isolated stairway that serves as a required exit; or

another sole-occupancy unit.

(2) A doorway in a Class 2 or 3 building must be protected if it provides access from a room not within a sole-occupancy unit to—

a public corridor, public lobby, or the like; or

the landing of an internal non fire-isolated stairway that serves as a required exit.

(3) A doorway in a Class 4 part of a building must be protected if it provides access to any other internal part of the building.

(4) Except as provided in (5), protection for a doorway must be at least—

in a building of Type A construction — a self-closing –/60/30 fire door; and

in a building of Type B or C construction — a self-closing, tight fitting, solid core door, not less than 35 mm thick.

(5) In a Class 3 building used as a residential care building protected with a sprinkler system complying with Specification 17, protection for a doorway must be at least—

a tight fitting, solid core door not less than 35 mm thick if the building is divided into floor areas not exceeding 500 m2 with smoke proof walls complying with S11C2; or

a tight fitting, solid core door not less than 35 mm thick fitted with a self-closing device, a delayed closing device or an automatic closing device.

(6) Other openings in internal walls which are required to have an FRL with respect to integrity and insulation must not reduce the fire-resisting performance of the wall.

(7) A door required by (4) or (5) may be automatic-closing in accordance with the following:

The automatic-closing operation must be initiated by the activation of a smoke detector, or any other detector deemed suitable in accordance with AS 1670.1 if smoke detectors are unsuitable in the atmosphere, installed in accordance with the relevant provisions of AS 1670.1 and located not more than 1.5 m horizontal distance from the approach side of the doorway.

Where any other required suitable fire alarm system, including a sprinkler system (other than a FPAA101D system) complying with Specification 17, is installed in the building, activation of the system must also initiate the automatic-closing operation.

(8) The requirements of (9) apply in a Class 2 or 3 building where a path of travel to an exit—

does not provide a person seeking egress with a choice of travel in different directions to alternative exits; and

is along an open balcony, landing or the like; and

passes an external wall of—

another sole-occupancy unit; or

a room not within a sole-occupancy unit.

(9) The external wall mentioned in (8)(c) must—

be constructed of concrete or masonry, or be lined internally with a fire-protective covering; and

have any doorway fitted with a self-closing, tight-fitting solid core door not less than 35 mm thick; and

have any windows or other openings—

protected internally in accordance with C4D5; or

located at least 1.5 m above the floor of the balcony, landing or the like.

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One C4D12.
Can't meet C4D12? A Performance Solution must meet the Performance Requirements it satisfies: C1P1, C1P2, C1P3, C1P4, C1P5, C1P6, C1P7, C1P8, C1P9. Start a Performance Solution →

State and territory variations all clauses side by side →