Deemed-to-Satisfy Provision · NCC 2022 Volume One

E1D13 Where sprinklers are required: occupancies of excessive hazard

Part E1 Fire fighting equipment · NCC 2019: Table E1.5 (Note 4)

Open E1D13 on NCC Online ↗
Varied in VIC. Check the variation for your state.

(1) In occupancies of excessive hazard, sprinklers are required in fire compartments where either of the following apply:

A floor area of more than 2 000 m2.

A volume of more than 12 000 m3.

(2) For the purposes of (1), occupancies of excessive fire hazard comprise buildings which contain—

hazardous processes or storage including the following:

Aircraft hangars.

Cane furnishing manufacture, processing and storage.

Fire-lighter and fireworks manufacture and warehousing.

Foam plastic and foam plastic goods manufacture, processing and warehousing e.g. furniture factory.

Hydrocarbon based sheet product, manufacture, processing and warehousing e.g. vinyl floor coverings.

Woodwool and other flammable loose fibrous material manufacture.

combustible goods with an aggregate volume exceeding 1000 m3 and stored to a height greater than 4 m including the following:

Aerosol packs with flammable contents.

Carpets and clothing.

Electrical appliances.

Combustible compressed fibreboards (low and high density) and plywoods.

Combustible cartons, irrespective of content.

Esparto and other fibrous combustible material.

Furniture including timber, cane and composite, where foamed rubber or plastics are incorporated.

Paper storage (all forms of new or waste) e.g. bales, sheet, horizontal or vertical rolls, waxed coated or processed.

Textiles raw and finished, e.g. rolled cloth, clothing and manchester.

Timber storage including sheets, planks, boards, joists and cut sizes.

Vinyl, plastic, foamed plastic, rubber and other combustible sheets, offcuts and random pieces and rolled material storage, e.g. carpet, tar paper, linoleum, wood veneer and foam mattresses.

All materials having wrappings or preformed containers of foamed plastics.

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One E1D13.
Can't meet E1D13? A Performance Solution must meet the Performance Requirements it satisfies: E1P1, E1P2, E1P3, E1P4, E1P5, E1P6. Start a Performance Solution →

State and territory variations all clauses side by side →

Defined terms used