E1D5 Where sprinklers are required: all classifications
Part E1 Fire fighting equipment · NCC 2019: Table E1.5
Sprinklers are required throughout the whole building if any part of the building has an effective height of more than 25 m—
including an open-deck carpark within a multi-classified building; but
excluding—
an open-deck carpark being a separate building; and
a Class 8 electricity network substation, with a floor area not more than 200 m2, located within a multi-classified building.
Changed in NCC 2025. See NCC 2025 Volume One E1D5, or show what changed.
Sprinklers are required throughout the whole building if any part of the building has an effective height of more than 25 m m. Exemptions E1D5 does not apply to — including an a class 7a open-deck carpark within a multi-classified building; but excluding — an open-deck carpark being that is a separate building; and or a Class 8 electricity network substation, substation with a floor area not more than 200 m2, m2 located within a multi-classified building.