Deemed-to-Satisfy Provision · NCC 2022 Volume One
E1D6 Where sprinklers are required: Class 2 and 3 buildings other than residential care buildings
Part E1 Fire fighting equipment · NCC 2019: Table E1.5
(1) In a Class 2 or 3 building, or any multi-classified building containing a Class 2 or 3 part, sprinklers are required throughout the whole building if any part of the building has—
a rise in storeys of 4 or more; and
an effective height of not more than 25 m.
(2) The requirements of (1) do not apply to a residential care building.
Changed in NCC 2025. See NCC 2025 Volume One E1D6, or show what changed.
(1) In a Class 2 or 3 building, or any … m. (2) The requirements of (1) do not apply to — a residential care building; and a Class 8 electricity network substation with a floor area not more than 200 m2 located within a multi-classified building.
Removed words are struck through; added words are highlighted. Comparison of the text only.
Can't meet E1D6? A Performance Solution must meet the Performance Requirements it satisfies: E1P1, E1P2, E1P3, E1P4, E1P5, E1P6. Start a Performance Solution →