E3D11 Fire service recall control switch
Part E3 Lift installations · NCC 2019: E3.9
(1) Each group of lifts must be provided with one fire service recall control switch required by E3D9 that activates the fire service recall operation at (6).
(2) The switch required by (1) must—
be located at the landing nominated by the appropriate authority; and
be labelled “FIRE SERVICE” in indelible white lettering on a red background; and
have two positions with an “OFF” and an “ON” position identified; and
be operable only by the use of a key that is removable in either the “OFF” position or the “ON” position.
(3) Adhesive labels must not be used for compliance with (2)(b) and (c).
(4) The key in (2)(d) must be able to turn all fire service recall control switches in the building and must have a different key combination to other keys used for lifts in the building.
(5) The fire service recall operation must be activated by—
switching the fire service recall control switch in (1) to “ON”; or
a signal from a fire management system approved by the appropriate authority.
(6) The activation of the fire service recall operation at (5) must—
cancel all registered car and landing calls; and
inactivate all door reopening devices that may be affected by smoke; and
ensure lift cars travelling toward the nominated floor continue to the nominated floor without stopping; and
ensure lift cars travelling away from the nominated floor stop at or before the next available floor without opening the doors (either automatically or by the door open button), reverse direction and travel without stopping to the nominated floor; and
for lifts stopped at a floor other than the nominated floor, close the doors and travel without stopping to the nominated floor; and
ensure that lifts stay at the nominated floor with doors open; and
permit all lifts to return to normal service if the fire service recall control switch at (1) is switched to the “OFF” position during or after the fire service recall operation.
(7) The requirements of (6) do not apply to lifts on inspection service or when the lift car fire service control switch required by E3D12 is in the "ON" position.
(8) Lifts having manual controls must signal an alert to the lift for the lift to return to the nominated floor containing the recall switch that activated the signal.
Changed in NCC 2025. See NCC 2025 Volume One E3D11, or show what changed.
(1) Each group of lifts must be provided with one a single fire service recall control switch required by E3D9 that activates … nominated floor containing the recall switch that activated the signal. (9) A key required by (2)(d) must be stored within a secure enclosure in accordance with (10) located — if there is FDCIE, beside the FDCIE; or if there is no FDCIE — within the fire control centre; or adjacent to the fire service recall switch. (10) The secure enclosure in (9) must — be securely attached to the wall; and be openable using a device suitable for use by the fire brigade; and be labelled “FIRE SERVICE LIFT KEYS” in capital letters not less than 20 mm in height and in a colour contrasting with the background.