Deemed-to-Satisfy Provision · NCC 2022 Volume One

E3D4 Warning against use of lifts in fire

Part E3 Lift installations · NCC 2019: E3.3

Open E3D4 on NCC Online ↗

(1) A warning sign must be displayed where it can be readily seen near every call button for a passenger lift or group of lifts throughout a building.

(2) The requirements of (1) do not apply to a small lift such as a dumb-waiter or the like that is for the transport of goods only.

(3) Each warning sign required by (1) must comply with the details and dimensions of Figure E3D4 and consist of—

incised, inlaid or embossed letters on a metal, wood, plastic or similar plate securely and permanently attached to the wall; or

letters incised or inlaid directly into the surface of the material forming the wall.

Figure E3D4 Warning sign for passenger lifts

Changed in NCC 2025. See NCC 2025 Volume One E3D4, or show what changed.

(1) A warning sign must be displayed where it can … E3D4 and consist of — incised, inlaid or embossed letters in a colour contrasting with the background on a metal, wood, plastic or similar plate securely and permanently attached to the wall; or letters Letters in a colour contrasting with the background incised or inlaid directly into the surface of the material forming the wall. Figure E3D4 Warning sign for passenger lifts

Removed words are struck through; added words are highlighted. Comparison of the text only.

Can't meet E3D4? A Performance Solution must meet the Performance Requirements it satisfies: E3P1, E3P2, E3P3, E3P4. Start a Performance Solution →