Deemed-to-Satisfy Provision · NCC 2022 Volume One

E3D3 Stretcher facility in lifts

Part E3 Lift installations · NCC 2019: E3.2

Open E3D3 on NCC Online ↗

(1) A stretcher facility in accordance with (2) must be provided—

in at least one emergency lift required by E3D5; or

where an emergency lift is not required, if passenger lifts are installed to serve any storey above an effective height of 12 m, in at least one of those lifts to serve each floor served by the lifts.

(2) A stretcher facility must accommodate a raised stretcher with a patient lying on it horizontally by providing a clear space not less than 600 mm wide x 2000 mm long x 1400 mm high above the floor level.

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One E3D3.
Can't meet E3D3? A Performance Solution must meet the Performance Requirements it satisfies: E3P1, E3P2, E3P3, E3P4. Start a Performance Solution →