Deemed-to-Satisfy Provision · NCC 2022 Volume One

E4D2 Emergency lighting requirements

Part E4 Visibility in an emergency, exit signs and warning systems · NCC 2019: SA E4.2(b)(iii), (j), E4.2

Open E4D2 on NCC Online ↗
Varied in SA. Check the variation for your state.

An emergency lighting system must be installed—

in every fire-isolated stairway, fire-isolated passageway or fire-isolated ramp; and

in every storey of a Class 5, 6, 7, 8 or 9 building where the storey has an area more than 300 m2—

in every passageway, corridor, hallway, or the like, that is part of the path of travel to an exit; and

in any room having a floor area more than 100 m2 that does not open to a corridor or space that has emergency lighting or to a road or open space; and

in any room having a floor area more than 300 m2; and

in every passageway, corridor, hallway, or the like, having a length of more than 6 m from the entrance doorway of any sole-occupancy unit in a Class 2 or 3 building or Class 4 part of a building to the nearest doorway opening directly to—

a fire-isolated stairway, fire-isolated passageway or fire-isolated ramp; or

an external stairway serving instead of a fire-isolated stairway under D2D13; or

an external balcony leading to a fire-isolated stairway, fire-isolated passageway or fire-isolated ramp; or

a road or open space; and

in every required non-fire-isolated stairway; and

in a sole-occupancy unit in a Class 5, 6 or 9 building if—

the floor area of the unit is more than 300 m2; and

an exit from the unit does not open to a road or open space or to an external stairway, passageway, balcony or ramp, leading directly to a road or open space; and

in every room or space to which there is public access in every storey in a Class 6 or 9b building if—

the floor area in that storey is more than 300 m2; or

any point on the floor of that storey is more than 20 m from the nearest doorway leading directly to a stairway, ramp, passageway, road or open space; or

egress from that storey involves a vertical rise within the building of more than 1.5 m, or any vertical rise if the storey concerned does not admit sufficient light; or

the storey provides a path of travel from any other storey required by (i), (ii) or (iii) to have emergency lighting; and

in a Class 9a health-care building—

in every passageway, corridor, hallway, or the like, serving a treatment area or a ward area; and

in every room having a floor area of more than 120 m2 in a patient care area; and

in every Class 9c building excluding within sole-occupancy units; and

in every required fire control centre.

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One E4D2.
Can't meet E4D2? A Performance Solution must meet the Performance Requirements it satisfies: E4P1, E4P2, E4P3. Start a Performance Solution →