E4D2 Emergency lighting requirements
Part E4 Visibility in an emergency, exit signs and warning systems · NCC 2019: SA E4.2(b)(iii), (j), E4.2
An emergency lighting system must be installed—
in every fire-isolated stairway, fire-isolated passageway or fire-isolated ramp; and
in every storey of a Class 5, 6, 7, 8 or 9 building where the storey has an area more than 300 m2—
in every passageway, corridor, hallway, or the like, that is part of the path of travel to an exit; and
in any room having a floor area more than 100 m2 that does not open to a corridor or space that has emergency lighting or to a road or open space; and
in any room having a floor area more than 300 m2; and
in every passageway, corridor, hallway, or the like, having a length of more than 6 m from the entrance doorway of any sole-occupancy unit in a Class 2 or 3 building or Class 4 part of a building to the nearest doorway opening directly to—
a fire-isolated stairway, fire-isolated passageway or fire-isolated ramp; or
an external stairway serving instead of a fire-isolated stairway under D2D13; or
an external balcony leading to a fire-isolated stairway, fire-isolated passageway or fire-isolated ramp; or
a road or open space; and
in every required non-fire-isolated stairway; and
in a sole-occupancy unit in a Class 5, 6 or 9 building if—
the floor area of the unit is more than 300 m2; and
an exit from the unit does not open to a road or open space or to an external stairway, passageway, balcony or ramp, leading directly to a road or open space; and
in every room or space to which there is public access in every storey in a Class 6 or 9b building if—
the floor area in that storey is more than 300 m2; or
any point on the floor of that storey is more than 20 m from the nearest doorway leading directly to a stairway, ramp, passageway, road or open space; or
egress from that storey involves a vertical rise within the building of more than 1.5 m, or any vertical rise if the storey concerned does not admit sufficient light; or
the storey provides a path of travel from any other storey required by (i), (ii) or (iii) to have emergency lighting; and
in a Class 9a health-care building —
in every passageway, corridor, hallway, or the like, serving a treatment area or a ward area; and
in every room having a floor area of more than 120 m2 in a patient care area; and
in every Class 9c building excluding within sole-occupancy units; and
in every required fire control centre.