South Australia variation · NCC 2022 Volume One

SA E4D2 Emergency lighting requirements

Part E4 Visibility in an emergency, exit signs and warning systems · varies E4D2 Emergency lighting requirements

Open on NCC Online ↗

Delete clause E4D2 and insert SA E4D2 as follows:

An emergency lighting system must be installed—

in every fire-isolated stairway, fire-isolated passageway or fire-isolated ramp; and

in every storey of a Class 5, 6, 7, 8 or 9 building where the storey has a floor area more than 300 m2—

in every passageway, corridor, hallway, or the like, that is part of the path of travel to an exit; and

in any room having a floor area more than 100 m2 that does not open to a corridor or space that has emergency lighting or to a road or open space; and

in any room having a floor area more than 300 m2, except that—

in a farm building any area primarily used for the storage of hay can be excluded when calculating the floor area of the storey or room of the building for the purpose of determining emergency lighting requirements; and

emergency lighting is not required in a farm building where automatic back-up power is provided by a fuel driven back-up generator or where no artificial lighting is provided in the building; and

an emergency lighting system is not required in a farm shed, Group C farm building or at ground floor level in cell type silos or storage sheds; and

in a bulk grain storage facility the spacing of emergency lights can be increased to twice the distance required for Class 7 buildings; and

in every passageway, corridor, hallway, or the like, having a length of more than 6 m from the entrance doorway of any sole-occupancy unit in a Class 2 or 3 building or Class 4 part of a building to the nearest doorway opening directly to—

a fire-isolated stairway, fire-isolated passageway or fire-isolated ramp; or

an external stairway serving instead of a fire-isolated stairway under D2D13; or

an external balcony leading to a fire-isolated stairway, fire-isolated passageway or fire-isolated ramp; or

a road or open space; and

in every required non-fire-isolated stairway; and

in a sole-occupancy unit in a Class 5, 6 or 9 building if—

the floor area of the unit is more than 300 m2; and

an exit from the unit does not open to a road or open space or to an external stairway, passageway, balcony or ramp, leading directly to a road or open space; and

in every room or space to which there is public access in every storey in a Class 6 or 9b building if—

the floor area in that storey is more than 300 m2; or

any point on the floor of that storey is more than 20 m from the nearest doorway leading directly to a stairway, ramp, passageway, road or open space; or

egress from that storey involves a vertical rise within the building of more than 1.5 m, or any vertical rise if the storey concerned does not admit sufficient light; or

the storey provides a path of travel from any other storey required by (i), (ii) or (iii) to have emergency lighting; and

in a Class 9a health-care building—

in every passageway, corridor, hallway, or the like, serving a treatment area or a ward area; and

in every room having a floor area of more than 120 m2 in a patient care area; and

in every Class 9c building excluding within sole-occupancy units; and

in every required fire control centre; and

in an underground passage in a bulk grain storage facility.

Not in NCC 2025. No SA E4D2 in NCC 2025 Volume One.